Rated for 1200 amps, this Series G NG-Frame circuit breaker incorporates a sophisticated Digitrip 310+ electronic trip unit. The comprehensive LSIG configuration allows precise tuning of long-time, short-time, instantaneous, and ground fault parameters. Designed with stud/tapped pad terminals, the bolt-on breaker integrates into Eaton Series G panelboards and motor control centers. Facilities can also cross-reference this unit to the newer Power Defense PDG53M1200E3NN model.
What does the "E" suffix mean in the NGH312036E catalog number?
The "E" suffix indicates that this circuit breaker is equipped with imperial tapped line and load conductors rather than metric hardware or pre-installed mechanical lugs.
Do I need to order wiring lugs separately for the NGH312036E?
Yes. This breaker comes standard with imperial tapped pad connections designed for direct busbar mounting. If your installation requires standard cable wiring, you must purchase compatible NG-frame lug kits (such as the Eaton TA1200NB1) separately.
Which enclosures and distribution equipment accept this 1200A NG-frame breaker?
The NGH312036E is designed for bolt-on installation in Eaton Series G Panelboards, Switchboards, and Motor Control Centers that are configured to accommodate the physical footprint of the 1200A NG-frame.
How does the NGH series differ from standard NG-frame circuit breakers?
The "H" in the NGH prefix identifies this as a high-interrupting capacity breaker. It is certified to safely clear fault currents up to 100kA at 240VAC and 65kA at 480VAC, offering elevated protection compared to standard-tier Series G models.
What tuning flexibility does the LSIG Digitrip 310+ trip unit offer?
The LSIG function provides adjustable settings for Long-Time, Short-Time, Instantaneous, and Ground-Fault protection. This allows panel builders to precisely tailor the trip curve to match specific load profiles, manage motor inrush currents, and achieve selective coordination with downstream protective devices.
Is equipment ground-fault protection integrated into this breaker?
Yes. The "G" in the LSIG trip function indicates built-in, adjustable equipment ground-fault protection. It allows you to configure both the pickup current and time delay. Note that if applied in a 4-wire system, an external neutral current transformer (such as the NGFCT120) may be required to properly calculate unbalanced ground-fault currents.
Does this breaker offer a flat-response short-time delay?
Yes. Because this breaker features the LSIG trip unit (indicated by the 36 catalog suffix), it provides a flat-response short-time delay action. This configuration offers better short-circuit selective coordination with downstream devices compared to the standard I2t ramp response found in standard LS trip units.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.