Built for high-amperage power distribution, the Eaton RD320T32W is a 2000A molded case circuit breaker from the proven Series C lineup. It utilizes a Digitrip 310 RMS electronic trip unit with adjustable LSI settings. This 3-pole R-Frame breaker is designed for bolt-on mounting within Eaton Series C panelboards, switchboards, and motor control centers. With an interrupting capacity of 65 kAIC at 480VAC, it handles severe faults. The unit features true RMS sensing and is HACR rated.
Eaton Series C Panelboards, Switchboards, Motor Control Centers
Protection and operation
Trip Technology
Electronic Trip
Trip Function Code
LSI
Trip Function
Long-Time, Short-Time, Instantaneous
Trip Adjustability
Adjustable
Standards and features
Available Options
Rating Plugs, Shunt Trip, Auxiliary Switch, Undervoltage Release, Bell Alarm, Padlock Attachment, Motor Operator, Lug Kits
Accessories
Digitrip RMS 310 Electronic Trip Unit
Standards
CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489
Approval
CE, CSA, UL
Temp Rating
40C
Construction Features
HACR Rated, Reverse Feed, True RMS Sensing, Interchangeable Trip Unit
Product FAQs
5 answers
What type of trip unit is included with the RD320T32W?
This breaker is equipped with a Digitrip 310 RMS solid-state electronic trip unit. It provides true RMS sensing and features adjustable Long-Time, Short-Time, and Instantaneous (LSI) settings for precise coordination in your power distribution system.
What enclosures are compatible with this R-Frame circuit breaker?
The RD320T32W is designed for bolt-on installation in Eaton and Cutler-Hammer Series C panelboards, switchboards, and motor control centers. It is also backward compatible with legacy Westinghouse equipment that accepts Series C R-Frame breakers.
How can I verify the operation of the electronic trip unit in the field?
The Digitrip 310 RMS trip unit on this breaker can be field-tested using the Eaton Seltronic test kit, catalog number SKT2. This allows technicians to verify the electronic trip functions and mechanical tripping action during routine maintenance.
What routine maintenance is recommended for this 2000A breaker?
Eaton recommends periodically cleaning the breaker surface with a dry, lint-free cloth or vacuum. You should also manually exercise the mechanism using the Push-to-Trip button and inspect all terminal connections for signs of overheating or discoloration. Do not blow debris into the breaker mechanism.
Does this breaker replace older Westinghouse 2000A R-Frame models?
Yes. Eaton acquired the Cutler-Hammer and Westinghouse circuit breaker divisions. The RD320T32W serves as the direct equivalent for legacy Westinghouse Series C R-Frame breakers with matching voltage, amperage, and LSI trip characteristics.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.