Built to protect circuits against overloads and short circuits, the Eaton PDG22M0060TFFJ is a 60A, 2-pole molded case circuit breaker. It has a 65kA interrupting rating at 480VAC. The thermal magnetic trip uses fixed thermal and fixed magnetic settings. Its LI trip function provides long-time and instantaneous protection. Terminal connections are line and load side lug.
How should I use the 60A rating when selecting the Eaton PDG22M0060TFFJ?
The rated current is 60A. Use that rating when coordinating the circuit's load, conductor ampacity and required overcurrent protection.
What voltage ratings should I use for AC and DC circuit selection?
The breaker is rated 600VAC and 250VDC. Use the rating that corresponds to the circuit's supply type, and keep the circuit voltage within that rating.
How does the 65kA interrupting rating affect selection for a 480VAC circuit?
The interrupting rating is 65kA at 480VAC. For a 480VAC installation, compare the available fault current at the installation point with this rating; it must not exceed 65kA.
What protection does the thermal-magnetic LI trip provide?
The thermal-magnetic LI trip combines long-time overload protection with instantaneous short-circuit protection. The thermal element responds to sustained overloads, while the magnetic element responds rapidly to high fault current.
Can I adjust the thermal or magnetic trip settings?
Both the thermal and magnetic trip settings are fixed. Choose this breaker when fixed trip settings meet the circuit's protection requirements, rather than when field-adjustable trip settings are needed.
When should I select this two-pole breaker?
This is a two-pole breaker for single-phase applications. Use the pole count and phase rating to select it for a circuit requiring two-pole overcurrent protection.
How are conductors terminated on the line and load sides?
Both the line and load sides use lug connections. Plan for lug terminations for the incoming supply conductors and outgoing circuit conductors.
What dimensions should I account for in the installation layout?
The breaker measures 6 in high, 2.75 in wide and 3.5 in deep. Use these dimensions to plan its physical space, while allowing separate room for conductor routing and termination access.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.