Eaton/Cutler-Hammer PDG22P0150TFFL 2 Pole Circuit Breaker
The Eaton/Cutler-Hammer PDG22P0150TFFL is a 2 Pole thermal magnetic molded case circuit breaker with a current rating of 150 Amps and a voltage rating of 600VAC. It has an interrupting rating of 100kAIC at 480VAC. The PDG22P0150TFFL has a bolt-on connection type and includes long time and instantaneous trip functions.
Eaton Pow-R-Line Xpert Panelboards and Switchboards
Wire Gauge
4 AWG - 4/0 AWG
Max Wire
4/0 AWG
Min Wire
4 AWG
Protection and operation
Trip Technology
Thermal Magnetic
Trip Function Code
LI
Trip Function
Long-time, Instantaneous
Trip Adjustability
Fixed Thermal, Fixed Magnetic
Standards and features
Standards
RoHS
Approval
CSA, CCC, IEC, UL, CE
Product FAQs
7 answers
What type of trip unit is installed in the PDG22P0150TFFL?
This breaker features a fixed thermal, fixed magnetic (TFF) trip unit. It provides standard long-time and instantaneous (LI) protection for general-purpose applications without adjustable settings.
What terminal configuration is included with the PDG22P0150TFFL?
The "L" suffix in the catalog number indicates it comes factory-equipped with standard load-side lugs only. Line-side connections or alternative terminal kits must be sourced separately.
What are the physical dimensions of this 2-pole Frame 2 breaker?
The PDG22P0150TFFL measures 6.00 inches in height, 2.75 inches in width, and 3.50 inches in depth.
Is the PDG22P0150TFFL suitable for international equipment?
Yes. The "PDG" prefix stands for Power Defense Globally Rated. It carries multiple international approvals, including UL, CSA, IEC, and CCC, making it ideal for global OEM panels.
What does the "P" in the PDG22P0150TFFL catalog number signify?
The "P" designates the specific interrupting capacity tier for this Frame 2 breaker, which corresponds to its 100kAIC rating at 480VAC.
Does this specific breaker model include an ArcFlash Reduction Maintenance System (ARMS)?
No. While the Power Defense platform offers ARMS technology on models with advanced PXR electronic trip units, the PDG22P0150TFFL utilizes a basic thermal-magnetic trip unit that does not support this feature.
Can the Power Defense PDG22P0150TFFL replace older Eaton Series C breakers?
Yes. The Power Defense Frame 2 (PDG2) series is designed as a modern replacement for legacy Eaton Series C F-Frame breakers. However, while the physical footprint is similar, external accessories like handle mechanisms and covers are not interchangeable between the two series.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.