Providing comprehensive circuit protection, the Eaton NGC312039E is a 3-pole, 1200A Series G molded case circuit breaker. It features a Digitrip 310+ electronic trip unit for configurable coordination. This bolt-on NG-frame breaker installs into Eaton Pow-R-Line C panelboards and switchboards. It utilizes imperial tapped terminals and is 80% rated. Rated for 100 kAIC at 480VAC, it delivers ALSIG protection with ground fault sensing and an Arcflash Reduction Maintenance System.
Does the Eaton NGC312039E come with lug terminals included?
No. Eaton NG-frame circuit breakers do not ship with lugs. The unit is equipped with standard imperial-tapped stud and pad terminals for bolt-on connections. You must source the appropriate line and load lugs separately based on your specific wire size requirements.
What thread standard is used for the terminal pads on this breaker?
The "E" suffix at the end of the catalog number signifies that the breaker uses imperial-tapped line and load conductor terminals. Metric mounting hardware cannot be used on this specific unit.
Can the Eaton NGC312039E be used in reverse feed applications?
Yes. All Eaton NG-frame molded case circuit breakers are suitable for reverse feed installations.
Is the NGC312039E considered a 100% or 80% rated circuit breaker?
This unit is a standard 80% rated circuit breaker. In Eaton's Series G nomenclature, a 100% rated version of this frame would require a "C" suffix in the catalog number.
What does the "39" in the catalog number indicate about the trip unit?
The "39" indicates the breaker is equipped with a Digitrip 310+ electronic ALSIG trip unit. This provides fully adjustable Long-Time, Short-Time, Instantaneous, and Ground-Fault protection, as well as an integrated Arcflash Reduction Maintenance System (ARMS).
Does this breaker feature an energy-reducing maintenance switch?
Yes. The included ALSIG trip unit features Eaton's Arcflash Reduction Maintenance System (ARMS). When activated, this mode reduces the clearing time of the breaker during a fault, lowering the incident energy and improving safety for personnel working on energized equipment.
What electrical equipment is this circuit breaker designed to be installed in?
The NGC312039E is engineered for use within Eaton Series G panelboards, switchboards, motor control centers, and Pow-R-Line C panelboards.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 1 review.