Eaton/Cutler-Hammer PDD23F0100TFFL 3 Pole Circuit Breaker
The Eaton/Cutler-Hammer PDD23F0100TFFL is a 3 Pole thermal magnetic molded case circuit breaker with a current rating of 100 Amps and a voltage rating of 240VAC. It has an interrupting rating of 35kAIC at 240VAC. The PDD23F0100TFFL has a bolt-on connection type and includes long time and instantaneous trip functions.
What panelboards is the Eaton PDD23F0100TFFL compatible with?
This 100A, 3-pole breaker is engineered specifically for installation in Eaton Power Defense panelboards and switchboards. It utilizes a secure bolt-on connection to mount directly to the panel bus.
What does "TFFL" mean in the PDD23F0100TFFL catalog number?
In the Eaton Power Defense nomenclature, "TFF" indicates that the breaker is equipped with a thermal-magnetic trip unit featuring fixed thermal and fixed magnetic settings. The "L" designates that the unit includes standard lug terminals.
Can the PDD23F0100TFFL be used in DC voltage systems?
Yes. While it has a primary rating of 35kAIC at 240VAC, this breaker is dual-rated for both AC and DC applications. It provides a 10 kAIC interrupt rating at both 125VDC and 250VDC.
What safety and environmental certifications does this breaker carry?
The PDD23F0100TFFL is UL and CSA approved for North American installations. It is also HACR rated for use with heating, air conditioning, and refrigeration equipment, and meets RoHS environmental compliance standards.
Are field-installable accessories available for this breaker?
Yes, because it is built on the Power Defense Frame 2 (PDG/PDE) platform, it accepts a wide range of internal and external accessories. Compatible additions include auxiliary switches, shunt trips, undervoltage releases, alarm switches, padlock attachments, and rotary handle mechanisms.
Does the PDD23F0100TFFL offer adjustable trip settings?
No, this specific model features a standard thermal-magnetic trip unit with fixed thermal and fixed magnetic settings, providing basic long-time (L) and instantaneous (I) protection. Applications requiring field-adjustable pick-up points or advanced communication capabilities will require a Power Defense breaker equipped with a Power Xpert Release (PXR) electronic trip unit.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 2 reviews.