| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | PDG22F0150TFFJ |
| Series | PDG2 |
| Amperage | 150A |
| Poles | 2 |
| Mounting Style | Panel Mount |
| Voltage | 240VAC, 480VAC, 600VAC, 250VDC |
| Phase | 1 |
| AIC Rating | 35kA @ 240VAC, 25kA @ 480VAC, 14kA @ 600VAC, 10kA @ 250VDC |
| Terminal Type | Lugs |
|---|---|
| For Use With | Eaton Power Defense Enclosures, Panelboards |
| Wire Gauge | 4 AWG - 4/0 AWG (Al/Cu) |
| Max Wire | 4/0 AWG |
| Min Wire | 4 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Auxiliary Switch, Bell Alarm, Shunt Trip, Undervoltage Release, Handle Mechanism |
|---|---|
| Accessories | Line and Load Lugs Included |
| Standards | CSA C22.2 No. 5, IEC 60947-2, UL 489, RoHS |
| Approval | CCC, CE, CSA, IEC, RoHS, UL |
| Temp Rating | -20C to 70C |
| Construction Features | HACR Rated, RoHS Compliant |
Yes, Power Defense Frame 2 breakers are the direct modern replacements for legacy Eaton Series C F-Frame breakers of the same rating. However, because the physical mounting arrangement is different, you must use updated Power Defense mounting hardware during installation.
Yes. According to Eaton, Power Defense Frame 2 molded case circuit breakers with thermal-magnetic trip units can be safely reverse fed.
In the Eaton Power Defense catalog numbering system, TFF indicates the breaker is equipped with a thermal-magnetic trip unit featuring fixed thermal and fixed magnetic protection settings.
No. This specific model features a standard thermal-magnetic trip unit with Long-Time and Instantaneous (LI) protection only. It does not include ground fault equipment protection or electronic trip functions.
The J at the end of the catalog number indicates that this breaker comes factory-equipped with standard line and load side lugs.
Yes. Eaton specifies that Power Defense Frame 2 breakers can use legacy Series C F-Frame terminals, and vice versa.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.