| Brand | Eaton / Cutler-Hammer |
|---|---|
| Series | PDG2 |
| Amperage | 200A |
| Poles | 2 |
| Mounting Style | Panel Mount |
| Voltage | 240VAC, 480VAC, 600VAC, 250VDC |
| Phase | 1 |
| AIC Rating | 65kA @ 240VAC, 35kA @ 480VAC, 18kA @ 600VAC, 10kA @ 250VDC |
| Frame Type | Complete Breaker |
|---|---|
| Terminal Type | Lugs |
| For Use With | Eaton Pow-R-Line 1a, 2a, 3a, 4 Panelboards, Power Defense Enclosures |
| Wire Gauge | 4 AWG - 4/0 AWG |
| Max Wire | 4/0 AWG |
| Min Wire | 4 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Auxiliary Switch, Bell Alarm, Shunt Trip, Undervoltage Release, Padlock Attachment, Handle Mechanism, Terminal Shields |
|---|---|
| Accessories | Load Side Lugs Included (PDG2X2TA225) |
| Standards | CSA C22.2 No. 5, IEC 60947-2, UL 489, RoHS |
| Approval | CCC, CE, CSA, IEC, RoHS, UL |
| Temp Rating | -20C to 70C |
| Construction Features | RoHS Compliant, Globally Rated |
This Frame 2 breaker is compatible with Eaton Pow-R-Line 1a, 2a, 3a, and 4 panelboards, as well as dedicated Power Defense enclosures.
The factory lugs on this breaker accommodate wire sizes from 4 AWG to 4/0 AWG. Verify that your conductors are properly sized for a 200A load according to local electrical codes.
Yes, in addition to its AC ratings, this breaker is rated for 250VDC systems with a 10kAIC interrupting capacity.
The LI designation means the thermal-magnetic trip unit provides Long-Time protection for standard overloads and Instantaneous protection for short circuits.
No, this breaker features fixed thermal and fixed magnetic trip settings. Applications requiring adjustable trip thresholds will need a Power Defense model with an electronic trip unit.
Yes, this is a complete breaker. It includes the Power Defense Frame 2 body, the fixed thermal-magnetic trip unit, and standard lug terminals for panel mounting.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.