Eaton / Cutler-HammerPDG23F0060TFFL
Quantity
New
Quantity
Eaton / Cutler-HammerPDG23F0060TFFL
Eaton / Cutler-HammerPDG23G0060TFFJ
Eaton / Cutler-HammerPDG23G0060TFFL
Eaton / Cutler-HammerPDG23M0060TFFJ
| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | PDG23F0060TFFJ |
| Series | PDG2 |
| Amperage | 60A |
| Poles | 3 |
| Mounting Style | Panel Mount |
| Voltage | 240VAC, 480VAC, 600VAC, 250VDC |
| Phase | 3 |
| AIC Rating | 35kA @ 240VAC, 25kA @ 480VAC, 14kA @ 600VAC, 10kA @ 250VDC |
| Terminal Type | Lugs |
|---|---|
| For Use With | Eaton Power Defense Panelboards, Switchboards |
| Wire Gauge | 14 AWG - 1/0 AWG |
| Max Wire | 1/0 AWG |
| Min Wire | 14 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Motor Operator, Rotary Handle |
|---|---|
| Accessories | Line and Load Lugs Included |
| Standards | CSA C22.2 No. 5, IEC 60947-2, UL 489, RoHS |
| Approval | CCC, CE, CSA, IEC, RoHS, UL |
| Temp Rating | -20C to 70C |
| Construction Features | HACR Rated, RoHS Compliant, Current Limiting, Common Trip, Trip-Free Mechanism, Reverse Feed |
Yes, the Power Defense Frame 2 series is the modern replacement for legacy Cutler-Hammer Series C F-Frame breakers, such as the FDB3060. If you are retrofitting this into an older Pow-R-Line panelboard, you will need to replace the legacy mounting hardware with a new Pow-R-Line Xpert connector kit.
Yes, standard Eaton Power Defense Frame 2 molded case circuit breakers equipped with thermal-magnetic trip units can be safely reverse fed.
In the Power Defense nomenclature, the T indicates a thermal-magnetic trip unit. The double F specifies that both the thermal and magnetic trip settings are fixed. The J denotes that the breaker includes standard line and load side lugs.
The letter F designates the specific interrupting capacity tier for this Frame 2 breaker. It indicates a maximum interrupting rating of 25kAIC at 480VAC and 35kAIC at 240VAC.
The fixed thermal-magnetic trip unit provides long-time (L) protection against overloads and instantaneous (I) protection against short circuits. Both the thermal and magnetic trip points are factory preset and non-adjustable.
The included line and load lugs are designed to accept wire gauges ranging from 14 AWG to 1/0 AWG.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.