Part of the Quicklag family, the Eaton QB1015AFGF delivers dual function safety for commercial, industrial, and marine environments. It bolts securely into Eaton Pow-R-Line panelboards, utilizing a pigtail neutral for reliable combination AFCI and GFCI protection. Rated at 10 kAIC at 120VAC, this 15A single-pole breaker features a diagnostic LED and self-test functionality. It serves as a drop-in replacement for the legacy QBAFGF1015, offering non-interchangeable trips.
HACR Rated, SWD Rated, Non-Interchangeable Trip, Self-Test, Diagnostic LED
Product FAQs
8 answers
Which panelboards are compatible with the QB1015AFGF circuit breaker?
This bolt-on breaker is designed specifically for use in Eaton Pow-R-Line panelboards that accept Quicklag QB or BAB frame breakers.
Does the QB1015AFGF require a plug-on neutral load center?
No. This breaker features a pigtail neutral connection. The coiled white wire must be manually connected to the neutral bar of the panelboard, making it suitable for standard panels without plug-on neutral capabilities.
What type of protection does the QB1015AFGF provide?
It is a dual-function breaker that provides both Arc Fault Circuit Interrupter (AFCI) and Ground Fault Circuit Interrupter (GFCI) protection, in addition to standard thermal-magnetic overload and short-circuit protection.
Can this single-pole breaker be used on shared-neutral circuits?
No. According to Eaton installation guidelines, single-pole electronic breakers like the QB1015AFGF cannot be used to protect shared-neutral or multi-wire branch circuits.
Is it safe to perform a Megger or high-voltage test with this breaker installed?
No. You must remove the breaker prior to hi-pot or Megger testing of the circuit. High-voltage testing with the breaker in place can damage its internal electronic components.
Does the QB1015AFGF replace older Eaton dual-function breakers?
Yes, it serves as a direct drop-in replacement for the legacy QBAFGF1015 circuit breaker in Eaton Pow-R-Line panels.
How do I read the diagnostic LED trip code on this breaker?
After a trip, turn the breaker back on. The diagnostic LED will display a trip code after a 3-second startup delay, repeating the code for 30 iterations to help identify the specific cause of the fault.
Can the QB1015AFGF be reverse fed or backwired?
No. Eaton strictly prohibits reverse feeding or backwiring these electronic dual-function circuit breakers.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 1 review.