ABB / General ElectricTEYD2060B
Quantity
New
Quantity
ABB / General ElectricTEYD2060B
ABB / General ElectricTEYD2040B
ABB / General ElectricTEYD2070B
ABB / General ElectricTEYD2030B
| Brand | ABB / General Electric |
|---|---|
| Series | TEYD |
| Amperage | 50A |
| Poles | 2 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480Y/277VAC, 250VDC, 120/240VAC |
| Phase | 1 |
| AIC Rating | 65kA @ 240VAC, 25kA @ 480Y/277VAC, 10kA @ 250VDC, 65kA @ 120/240VAC |
| Frame Type | TEY |
|---|---|
| Terminal Type | Lugs |
| For Use With | GE A-Series Lighting Panelboards |
| Wire Gauge | 10-4 AWG (Cu/Al) |
| Max Wire | 4 AWG |
| Min Wire | 10 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Padlock Attachment, Mounting Base |
|---|---|
| Accessories | Load Side Lugs |
| Standards | CSA C22.2 No. 5, NEMA AB 1, UL 489 |
| Approval | CSA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, HID Rated, Common Trip, Quick-Make/Quick-Break, Non-Interchangeable Trip |
The TEYD2050B features a higher short-circuit interrupting rating. While the standard TEY2050B is rated for 14kA at 480/277VAC, the TEYD2050B is rated for 25kA at 480/277VAC, making it suitable for systems with higher available fault currents.
For the factory-installed lugs on the TEYD2050B, the recommended tightening torque is 60 in-lbs for 10 to 4 AWG copper or aluminum wire.
Yes. GE TEYD series circuit breakers do not have line and load markings and are suitable for reverse feed applications.
This breaker is designed for use in GE A-Series lighting panelboards, including Type AS, AD, and AE panels. It requires a bolt-on connection and occupies 1 inch of space per pole.
No. The TEYD2050B is a standard thermal-magnetic circuit breaker providing long-time and instantaneous (LI) overcurrent and short-circuit protection. It does not include GFCI or AFCI capabilities.
Yes. The TEYD2050B has a 25kA interrupting rating at 480/277VAC, which exceeds the 18kA rating of the TEYF2050B. It shares the same physical dimensions and bolt-on mounting, making it a safe and compliant upgrade where higher fault current ratings are required.
Yes. The TEYD2050B is HACR rated for use with heating, air conditioning, and refrigeration equipment. Because it is a 50A breaker, it is also HID rated for high-intensity discharge lighting circuits.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.