ABB / General ElectricTEYH2080B
Quantity
New
Quantity
ABB / General ElectricTEYH2080B
ABB / General ElectricTEYH2060B
ABB / General ElectricTEYH2090B
ABB / General ElectricTEYH2050B
| Brand | ABB / General Electric |
|---|---|
| Series | TEYH |
| Amperage | 70A |
| Poles | 2 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480Y/277VAC, 250VDC, 120/240VAC |
| Phase | 1 |
| AIC Rating | 65kA @ 240VAC, 35kA @ 480Y/277VAC, 10kA @ 250VDC, 65kA @ 120/240VAC |
| Frame Type | TEY |
|---|---|
| Terminal Type | Lugs |
| For Use With | GE A-Series Lighting Panelboards |
| Wire Gauge | 4-1/0 AWG (Cu/Al) |
| Max Wire | 1/0 AWG |
| Min Wire | 4 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Bell Alarm, Padlock Attachment, Mounting Base |
|---|---|
| Accessories | Load Lugs |
| Standards | CSA C22.2 No. 5, UL 489 |
| Approval | CSA, HACR, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Common Trip, Quick-Make/Quick-Break, Non-Interchangeable Trip, Reverse Feed |
This bolt-on breaker is designed exclusively for GE A-Series lighting panelboards. It bolts directly to the copper or aluminum bus of the panel interior and cannot be used in standard load centers.
The 'H' in the catalog number designates a high interrupting capacity. While a standard TEY breaker is typically rated for 14kAIC at 480/277V, the TEYH2070B provides 35kAIC at the same voltage. Both share the exact same physical dimensions and bolt-on mounting style.
No. Despite its compact size, this is a bolt-on molded case circuit breaker intended for direct bus connection in A-Series panelboards. It does not feature DIN rail mounting clips.
Yes, it carries a DC rating of 10kAIC at 250VDC. This makes it suitable for specific industrial DC control circuits or battery backup systems requiring a 70A 2-pole disconnect.
The factory-installed lugs accept both copper (Cu) and aluminum (Al) conductors ranging from 4 AWG to 1/0 AWG. Ensure proper application of joint compound if utilizing aluminum wiring.
Yes, if your fault current calculations require a higher interrupting rating, the TEYH2070B will physically fit in the same A-Series panel space as a standard TEY or TEYF breaker of the same pole configuration.
No, this model features standard thermal-magnetic trip functions (Long-Time and Instantaneous) for overload and short-circuit protection. It does not provide GFCI or AFCI capabilities.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.