General Electric THQL1130GFT2 1 Pole Ground Fault Circuit Breaker
The General Electric THQL1130GFT2 is a 1 Pole molded case ground fault circuit breaker with a current rating of 30 Amps and a voltage rating of 120VAC. It has an interrupting rating of 10kAIC. The THQL1130GFT2 has a plug-in connection type.
GE PowerMark Gold Load Centers, ABB ReliaHome Load Centers
Protection and operation
Trip Technology
Thermal Magnetic
Trip Function Code
LI
Trip Function
Long-time, Instantaneous
Trip Adjustability
Fixed Thermal, Fixed Magnetic
Standards and features
Special Classification
GFCI
Product FAQs
6 answers
What electrical panels are compatible with the THQL1130GFT2 circuit breaker?
This Q-Line plug-in breaker is designed for use in GE and ABB ReliaHome load centers, as well as legacy GE PowerMark Gold and PowerMark PRO panels that accept 1-inch THQL breakers.
What type of ground fault protection does the THQL1130GFT2 provide?
It provides Class A ground fault protection, meaning it is designed to trip when it detects a ground fault current of 5 milliamperes (5mA). The GFT2 designation also indicates it includes a built-in self-test feature to ensure the GFCI circuitry is functioning properly.
Does the THQL1130GFT2 require a pigtail connection for the neutral?
Yes, this model features a long pigtail neutral wire that must be connected to the neutral bus bar in the panel to properly power the ground fault circuitry.
What is the difference between the THQL1130GFT2 and the THQL1130PGFT2?
The THQL1130GFT2 uses a traditional pigtail wire that connects to the panel neutral bus bar. The THQL1130PGFT2 is the plug-on neutral version, which connects directly to the neutral bar without a pigtail, requiring a compatible plug-on neutral load center.
Can I use this 1-inch THQL breaker in place of a half-inch THQP breaker?
THQL breakers require a full 1-inch space per pole. They can be installed in panels that accept THQP breakers provided there is enough physical space, but they will take up twice the width of a THQP breaker.
What does the self-test feature on this GFCI breaker do?
The self-test function automatically and periodically tests the internal electronics of the breaker to confirm the ground fault protection is active. If the self-test detects a failure, the breaker will trip and prevent power from being delivered to ensure personnel safety.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.