ITE JL3T070-R 3 Poles Circuit Breaker

ITE 3 poles circuit breaker features a thermal magnetic molded case for extra protection. The circuit breaker has a current rating of 70 amps with a voltage rating of 600 v.

Specifications:

  • Manufacturer: ITE
  • Cat. No: JL3T070-R
  • Alternate Part No: JL3T070-R
  • Product Type: Circuit Breaker
  • Trip Unit Type: Thermal Magnetic
  • Frame Type: JL
  • Type: JL
  • Number Of Poles: 3
  • Voltage Rating: 600 V
  • Amperage Rating: 70 A
  • Functions: Long Time and Instantaneous Trip Functions
  • Authentic ITE Product

Specifications

Key specifications
Brand ITE
Part Number JL3T070-R
Series JL
Amperage 70 A
Poles 3
Voltage 600 V
Fit and installation
Frame Type JL
Protection and operation
Trip Technology Thermal Magnetic

Product FAQs

5 answers
Which panelboards accept the ITE JL3T070 circuit breaker?

This bolt-on circuit breaker is compatible with Siemens P4 and P5 panelboards, SB switchboards, motor control centers, and legacy ITE FC-1 enclosures.

What is the modern replacement for the legacy ITE JL3T070?

The ITE JL series is a legacy frame that is no longer in active production. For modern panel upgrades or replacements, the Siemens JD frame is the direct substitute. A 70-amp, 3-pole JD frame breaker can be used in place of the JL3T070.

What is the interrupting capacity (AIC) for the JL frame?

The JL frame provides a maximum interrupting rating of 65 kA at 240V, 35 kA at 480V, and 25 kA at 600V. Always verify that the available fault current at your installation point does not exceed these limits.

Is the trip unit on the JL3T070 interchangeable?

Yes, the JL frame features an interchangeable trip unit design. The 70-amp thermal-magnetic trip unit can be removed and replaced with other JL class trip units up to the 400-amp frame maximum if load requirements change.

What are the primary safety considerations when replacing a legacy ITE JL breaker?

Always de-energize the panelboard before servicing. Confirm that the available fault current at the line terminals does not exceed the breaker interrupting capacity, and ensure the busbar connections are torqued to the manufacturer specifications to prevent high-resistance faults.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.