Designed to protect circuits against overloads and short circuits, the Square D JJA32200 is a molded case circuit breaker. It has rated current of 200A, rated voltage of 240VAC and an interrupting rating of 100kA at 240VAC. This 3-pole, 3-phase PowerPacT J-frame, JJA-series breaker uses I-Line mounting and lug terminals. Thermal magnetic tripping provides long-time and instantaneous functions with fixed thermal and adjustable magnetic settings.

Specifications

Key specifications
Brand Square D
Part Number JJA32200
Series JJA
Amperage 200A
Poles 3
Mounting Style I-Line
Voltage 240VAC
Phase 3
AIC Rating 100kA @ 240VAC
Fit and installation
Frame Type J
Terminal Type Lugs
For Use With Square D I-Line Panelboards and Switchboards
Wire Gauge 3/0 AWG - 350 kcmil
Max Wire 350 kcmil
Min Wire 3/0 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Adjustable Magnetic
Standards and features
Available Options Alarm Switch, Auxiliary Switch, Motor Operator, Undervoltage Release
Standards CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489
Approval CE, CSA, IEC, NOM, UL
Temp Rating -25C to 70C
Construction Features HACR Rated, Current Limiting, Visual Trip Indicator

Product FAQs

6 answers
What circuit voltage should I check when selecting the Square D JJA32200?

The breaker is rated 240VAC. Check the circuit's AC voltage against this rating when selecting it.

How does the interrupting rating affect breaker selection?

The interrupting rating is 100kA at 240VAC. The available fault current at the installation point must not exceed that rating.

How does the thermal-magnetic trip protect the circuit?

The thermal element provides long-time overload protection, while the magnetic element provides instantaneous protection against short-circuit current. This gives the breaker separate responses to sustained overloads and high-current faults.

Which trip setting can I adjust on JJA32200?

The magnetic instantaneous pickup is adjustable, while the thermal overload setting is fixed. Use the magnetic adjustment to set the instantaneous response, rather than attempting to change the long-time thermal protection.

What conductor sizes can I terminate in the lugs?

The lug conductor range is 3/0 AWG through 350 kcmil. Use conductors within that range and size them to meet the circuit's ampacity requirements.

How do phase and pole count guide selection of JJA32200?

JJA32200 is a three-phase, three-pole breaker. Check the circuit's phase arrangement and required pole count as separate selection criteria.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.