Built for ground-fault equipment protection, the Schneider Electric M9R44225 miniature circuit breaker has a 300mA ground-fault sensitivity. This 25A, 2-pole breaker is rated 480Y/277VAC and belongs to the Multi9 family and GFP series. It uses DIN rail mounting, a toggle actuator and Type A-SI residual-current protection. Box lug terminals accept 18 AWG to 2 AWG wire. Standards are EN/IEC 61008-1 and UL 1053, with UL approval.
What circuit ratings should I check before selecting the Schneider Electric M9R44225?
The Schneider Electric M9R44225 is rated 25A for a single-phase circuit, with two poles and a 50/60Hz frequency rating. Use these ratings when reviewing the circuit current, pole count and supply frequency.
What conductor sizes and terminal torque should I use?
The box-lug terminals accept conductors from 18 AWG through 2 AWG. Select the conductor size for the circuit requirements within that range, then tighten the terminals to 31.0 lb-in (3.5 N·m).
How should I plan mounting space for this device?
This device mounts on DIN rail. Its dimensions are 3.2 in high, 1.4 in wide and 2.4 in long; use these dimensions to plan rail space and enclosure clearance.
What temperature limits should I consider for the installation?
The operating temperature range is -25 to 60 °C, and the calibration temperature is 40°C. Check the expected temperature at the device location against the operating range, and use 40°C as the calibration reference.
How do the toggle and trip indicator help during operation?
The toggle provides manual operation, while the trip indicator helps you recognize a trip during troubleshooting. Investigate the cause of a trip before restoring power.
How should I interpret the 480Y/277VAC voltage rating?
The 480Y/277VAC rating applies to a wye system. Check both the circuit voltage and the supply configuration when selecting the device.
How do I use the 10kAIC interrupting rating when selecting this device?
The interrupting rating is 10kAIC at 240VAC. For a 240VAC application, verify that the available fault current at the installation point does not exceed this interrupting rating.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.