Square D PGA36060CU33A Molded Case Circuit Breaker

  • 600A
  • 3 Pole
  • I-Line
Square D PGA36060CU33A
Molded Case Circuit Breaker
Brand Square D
SKU PGA36060CU33A
Select Item Condition
Earn 15950 SuperPoints
  • 600A
  • 3 Pole
  • I-Line

Quantity

Bulk Pricing
Send your parts list for a volume quote.

Square D PGA36060CU33A - 600A 3 Pole Molded Case Circuit Breaker

New

$15,950.00 In Stock

Quantity

Description

Square D PGA36060CU33A molded case circuit breaker is rated 600A and 600VAC with 3 poles, a 100% continuous load rating and 50/60Hz rated frequency. Interrupting ratings are 65kA at 240VAC, 35kA at 480VAC and 18kA at 600VAC. This PowerPacT P-Frame breaker has I-Line mounting, 3-phase ABC connection, standard protection and a load side lug terminal connection. The MicroLogic 5.0 electronic LSI trip has an adjustable 240-600A trip range and long-time pickup settings of 0.4-1 x Ir. Dimensions are 12.86 in high, 8.27 in wide and 8.05 in deep. Approvals are CE, UL, CSA, NEMA, IEC and NOM.

Specifications

Key specifications
Brand Square D
Part Number PGA36060CU33A
Series PGA
Amperage 600A
Poles 3
Mounting Style I-Line
Voltage 240VAC, 480VAC, 600VAC
Phase 3
AIC Rating 65kA @ 240VAC, 35kA @ 480VAC, 18kA @ 600VAC
Electrical ratings
Amperage Range 240-600A
Fit and installation
Frame Type PGA
Terminal Type Lugs
For Use With Square D I-Line Panelboards and Switchboards
Wire Gauge (3) 3/0 AWG - 500 kcmil (Cu/Al)
Max Wire 500 kcmil
Min Wire 3/0 AWG
Protection and operation
Trip Technology Electronic Trip
Trip Function Code LSI
Trip Function Long-Time, Short-Time, Instantaneous
Trip Adjustability Adjustable
Trip Unit Model MicroLogic 5.0
Standards and features
Available Options Alarm Switch, Auxiliary Switch, Motor Operator, Padlock Attachment, Shunt Trip, Undervoltage Release
Standards CSA C22.2 No. 5, HACR, IEC 60947-2, NEMA AB 1, UL 489
Approval CE, CSA, IEC, NOM, UL
Temp Rating -25C to 70C
Construction Features HACR Rated

Product FAQs

10 answers
Can the Square D PGA36060CU33A be selected for a 600A continuous load?

Its 600A rated current and 100% continuous load rating allow selection at the full rated current for continuous-load applications.

How do I select this breaker for circuit voltage and available fault current?

The breaker is rated 600VAC, with interrupting ratings of 65kA at 240VAC, 35kA at 480VAC and 18kA at 600VAC. At the circuit voltage, the interrupting rating must meet or exceed the available fault current at the installation point.

What protection functions does the MicroLogic 5.0 trip unit offer?

The MicroLogic 5.0 electronic trip unit provides LSI protection: long-time protection for overloads, short-time protection for short circuits with a delay, and instantaneous protection for high fault currents. These functions support protection coordination when selecting and setting the breaker.

How far can I adjust the long-time pickup?

The adjustable trip range is 240-600A, with long-time pickup adjustable from 0.4-1 x Ir. Set the pickup to suit the circuit's load and conductor protection requirements rather than assuming the 600A current rating is the required setting.

What conductor sizes and materials can I use at the load-side lugs?

The load-side lug conductor range is (3) 3/0 AWG to 500 kcmil, Cu/Al. Select copper or aluminum conductors within that range, with ampacity appropriate for the circuit.

What torque should I use for the load-side terminal connections?

The terminal torque is 442.5 lb-in for the load-side lug connections. Use a calibrated torque tool to achieve the required clamping force.

What dimensions should I use when planning the installation layout?

The breaker measures 12.86 in high, 8.27 in wide and 8.05 in deep. Use these body dimensions when planning equipment layout and installation space.

What phase and frequency ratings should I check before selecting this breaker?

This is a 3-pole breaker for 3-phase service with an ABC phase connection and a 50/60Hz frequency rating. Use the phase arrangement and operating frequency as electrical selection criteria.

When is the HACR rating relevant to breaker selection?

HACR refers to heating, air-conditioning and refrigeration applications. This rating is relevant when selecting protection for equipment that calls for an HACR-rated circuit breaker.

What operating temperature range should I use for installation planning?

The operating temperature range is -25 to 70 °C. Plan the installation so the breaker's operating temperature remains within that range.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.