Serving as a modern replacement for legacy HLD63600 units, this SENTRON series MCCB integrates seamlessly into commercial and industrial power systems. It installs into Siemens P4 or P5 panelboards and switchboards, requiring separate lug kits for cable connections. The TM240 trip unit features both adjustable thermal and magnetic settings, allowing precise tuning of long-time and instantaneous protection while maintaining a robust 65kA interrupt rating at 480VAC.
What are the thermal and magnetic adjustment ranges for the Siemens 3VA5460-6EF31-0AA0?
This breaker features a TM240 ATAM trip unit. The thermal overload protection is adjustable from 480A to 600A. The instantaneous short-circuit protection is adjustable from 2400A to 4800A, which is 4 to 8 times the nominal current rating.
Can the 3VA5460-6EF31-0AA0 be used to replace legacy Siemens breakers?
Yes, this 3VA5 SENTRON series molded case circuit breaker serves as a modern replacement for legacy Siemens HLD63600 circuit breakers. Verify physical dimensions and mounting hardware requirements when upgrading existing electrical panels.
Are terminal lugs included with the 3VA5460-6EF31-0AA0 circuit breaker?
No. The 0AA0 suffix indicates this breaker is supplied without terminal connections from the factory. You will need to purchase and install the appropriate lug kits separately based on your specific wire size and conductor material requirements.
What types of electrical distribution equipment is this 600A breaker designed for?
The 3VA5460-6EF31-0AA0 is designed for seamless integration into Siemens P4 and P5 panelboards, as well as commercial and industrial switchboards.
What is the enclosure rating for this molded case circuit breaker?
The 3VA5460-6EF31-0AA0 component itself carries an IP40 protection rating when properly installed in an enclosure.
Is this Siemens 3VA5460-6EF31-0AA0 breaker rated for reverse feeding?
Yes, this thermal-magnetic circuit breaker is suitable for reverse feed applications, allowing flexibility when wiring line and load connections.
Does this breaker provide protection for HVAC equipment?
Yes, it is HACR rated. This makes it strictly rated for protecting commercial heating, air conditioning, and heavy duty refrigeration systems.
Does this breaker include integrated ground fault protection?
No. The TM240 trip unit provides Long-Time and Instantaneous protection. It does not have ground fault protection capabilities. If ground fault monitoring is required, an external relay or a different electronic trip unit breaker is necessary.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 4.8 out of 5 based on 8 reviews.