Rated for 200kAIC at 480VAC, the Siemens CED63B100L operates as a high-performance current-limiting molded case circuit breaker. This 3-pole, 100-amp ED-frame device comes factory-equipped with line and load side lugs for straightforward wiring in Siemens enclosures and switchboards. Utilizing a fixed thermal-magnetic trip unit, it delivers reliable long-time and instantaneous protection while significantly reducing let-through energy during severe fault conditions.
CSA C22.2 No. 5, HACR Rated, IEC 60947-2, NEMA AB 1, UL 489
Approval
CE, CSA, IEC, UL
Temp Rating
40C
Construction Features
Current Limiting, Extra High Interrupting Capacity, HACR Rated, Reverse Feed, Non-Interchangeable Trip
Special Features
Current Limiting
Product FAQs
7 answers
What wire sizes are compatible with the lugs on the CED63B100L?
The factory-installed line and load lugs accept 10 AWG to 1/0 AWG copper or aluminum conductors.
What does the L signify in the CED63B100L catalog number?
The L indicates that the breaker comes factory-equipped with both line and load side lugs.
Is the Siemens CED63B100L a current-limiting circuit breaker?
Yes, the CED6 frame is a current-limiting molded case circuit breaker. This design reduces let-through energy during severe fault conditions, which can allow for higher series ratings with downstream equipment.
Can the CED63B100L be reverse fed?
Yes, Siemens ED frame circuit breakers can be reverse connected for flexible installation in enclosures and switchboards.
What breaker family does the CED63B100L belong to?
It is part of the Siemens Sentron series and utilizes the ED frame footprint.
Are the thermal and magnetic trip settings adjustable on this breaker?
No, the CED63B100L features a fixed thermal and fixed magnetic trip unit. The long-time and instantaneous protection settings are factory calibrated and cannot be adjusted in the field.
What type of equipment is designed to house this breaker?
This unit-mount breaker is designed for installation in compatible Siemens enclosures, switchboards, and motor control centers that accept ED frame devices.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.