Siemens HEG3B030B Molded Case Circuit Breaker

  • 30A
  • 3 Pole
  • Bolt-On
Siemens HEG3B030B
Molded Case Circuit Breaker
Brand Siemens
SKU HEG3B030B
Select Item Condition
Earn 685 SuperPoints
  • 30A
  • 3 Pole
  • Bolt-On

Quantity

Bulk Pricing
Send your parts list for a volume quote.

Siemens HEG3B030B - 30A 3 Pole Molded Case Circuit Breaker

Re-Certified

$685.00 In Stock

Quantity

Description

The Siemens HEG3B030B molded case circuit breaker protects circuits against overloads and short circuits. This 30A, 3-pole, 3-phase breaker is rated 65kAIC at 480V, with voltage ratings of 240VAC, 480VAC, 600Y/347VAC, 250VDC and 500VDC. The HEG series uses an EG frame with bolt-on mounting and a load side lug. Fixed thermal and fixed magnetic trip settings provide long-time and instantaneous protection.

Specifications

Key specifications
Brand Siemens
Part Number HEG3B030B
Series HEG
Amperage 30A
Poles 3
Mounting Style Bolt-On
Voltage 240VAC, 480VAC, 600Y/347VAC, 250VDC, 500VDC
Phase 3
AIC Rating 100kA @ 240VAC, 65kA @ 480VAC, 25kA @ 600Y/347VAC, 30kA @ 250VDC, 30kA @ 500VDC
Fit and installation
Frame Type EG
Terminal Type Lugs
For Use With Siemens P4 and P5 Panelboards, Switchboards
Wire Gauge 14-1/0 AWG
Max Wire 1/0 AWG
Min Wire 14 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Fixed Magnetic
Standards and features
Available Options Alarm Switch, Auxiliary Switch, Shunt Trip, Undervoltage Release
Standards NEMA AB 1, UL 489
Approval UL
Temp Rating 40C
Construction Features High Interrupting Capacity

Product FAQs

8 answers
How should I use the 30A rating when selecting the Siemens HEG3B030B?

The 30A rating is the breaker's rated current. Use it when coordinating circuit protection with the calculated load and conductor ampacity, including applicable continuous-load requirements.

How does the 65kAIC interrupting rating guide selection?

At 480V, the breaker has a 65kAIC interrupting rating. Compare that rating with the available fault current at the installation point; the available fault current must not exceed the interrupting rating.

Can I select this breaker for a DC circuit?

The breaker carries 250VDC and 500VDC ratings. For a DC circuit, use the applicable DC rating when selecting voltage protection rather than relying on an AC voltage rating.

What does the fixed thermal-magnetic trip mean in use?

The thermal element provides long-time overload protection, while the magnetic element provides instantaneous response to high fault current. Both are fixed, so select the breaker for the required protection rather than planning to adjust its trip settings.

What conductor sizes can I terminate at the load-side lug?

The conductor range is 14 AWG through 1/0 AWG. Choose a conductor within that range that also meets the circuit's ampacity requirements; the terminal range alone does not determine the correct conductor size.

What installation method and load connection does this breaker use?

This breaker uses bolt-on mounting and a load-side lug connection. Plan installation around the bolted mounting method and termination of the outgoing conductor at the load-side lug.

Is this a three-pole breaker for a three-phase circuit?

Yes. This is a three-pole, three-phase breaker. Use those characteristics when selecting protection for the phase conductors, together with the circuit's current and voltage requirements.

Which AC voltage ratings should I consider for my circuit?

The AC ratings are 240VAC, 480VAC and 600Y/347VAC. Select the rating that matches your circuit voltage and system configuration, using the 600Y/347VAC rating for a wye system.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.