Engineered for commercial and industrial applications, the Siemens HJXD63B250 is a 3-pole, 250A molded case circuit breaker from the Sentron series. It features a robust JD-frame design and provides reliable thermal-magnetic protection. This bolt-on MCCB is designed to install into Siemens P4 and P5 panelboards or switchboards. It comes standard without lugs, requiring separate kits for connection. Rated at 65kAIC at 480V, it delivers high interrupting capacity for demanding systems.
Which Siemens panelboards can accommodate the HJXD63B250 circuit breaker?
This Sentron JD-frame breaker is designed for installation in Siemens P4 and P5 panelboards, as well as compatible Siemens switchboards.
Are mounting lugs included with the HJXD63B250?
By default, Siemens HJXD6 series breakers are shipped without lugs. Standard aluminum line and load lugs for this frame are part number TA2J6500 (accepting 3/0 AWG to 500 kcmil copper or 4/0 AWG to 500 kcmil aluminum wire) and must be ordered separately unless an L suffix is specified in the catalog number.
What does the adjustable magnetic trip function on the HJXD63B250 allow me to do?
While the thermal overload protection remains fixed at 250 amps, the adjustable magnetic element permits electricians to fine-tune the instantaneous short-circuit trip point. This helps coordinate the breaker with motor inrush currents or downstream protective devices without nuisance tripping.
What is the difference between the Siemens JXD63B250 and the HJXD63B250?
The H designation indicates a high interrupting capacity. The standard JXD63B250 is rated for 35kAIC at 480VAC, whereas the HJXD63B250 delivers a higher interrupting rating of 65kAIC at 480VAC for commercial or industrial systems requiring greater fault current protection.
Can the HJXD63B250 be reverse fed?
Yes. Because it is assembled with a non-interchangeable trip unit, this breaker is UL listed for reverse feed applications, allowing power to flow from the load terminals to the line terminals when system design requires it.
Is the HJXD63B250 rated for direct current (DC) applications?
Yes, this thermal-magnetic breaker is rated for use on DC systems, providing up to 25kAIC interrupting capacity at 500VDC. It is commonly used in ungrounded battery backups, UPS systems, and industrial DC power networks.
Is the HJXD63B250 HACR rated?
Yes, this breaker is HACR rated, meaning it is certified to safely provide overcurrent and short-circuit protection for commercial heating, air conditioning, and refrigeration equipment circuits.
Can I swap out the trip unit on the HJXD63B250 to change its amperage?
No, the X in the HJXD prefix indicates that this is a factory-assembled breaker with a non-interchangeable trip unit. If future amperage adjustments are anticipated, you must use a standard HJD frame and purchase the trip units separately.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.