Built for heavy-duty industrial use, this 225A molded case circuit breaker belongs to the Siemens Sentron JD frame series. The unit mount design ensures a precise fit into Siemens Sentron panelboards (Type P4, P5, S4, S5), switchboards, and motor control centers. This legacy model is officially replaced by the newer 3VA Series. Featuring a fixed thermal and adjustable magnetic trip unit, it provides LI functions with a 65kAIC rating at 240VAC. It is also HACR rated.
What is the difference between the Siemens JXD63225 and the JXD63B225?
The B in the catalog number JXD63B225 indicates that the breaker is supplied from the factory without terminal lugs installed. Aside from the terminal configuration, the base JD frame breaker and its protective characteristics are identical.
Which terminal lugs are compatible with this JD frame circuit breaker?
If you need to add line and load terminals, the Siemens TA2J6500 aluminum lug kit is widely used for JD frame models. This kit accepts one cable per pole, accommodating 3/0 AWG to 500 kcmil copper or 4/0 AWG to 500 kcmil aluminum wire.
Can I add internal accessories to the JXD63B225 breaker?
Yes, this Sentron series circuit breaker supports field-installable accessories. Panel builders can add shunt trips, auxiliary switches, alarm switches, and undervoltage releases to meet specific control requirements.
How does the trip adjustability function on the JXD63B225?
This unit features a fixed thermal element for long-time overload protection and an adjustable magnetic element. The magnetic trip allows you to dial in the instantaneous short-circuit response, which helps coordinate with specific motor inrush currents.
Can this Siemens circuit breaker be reverse fed?
Yes, this molded case circuit breaker is reverse feed capable. You can wire the line and load connections in either direction without compromising the thermal magnetic protection.
Is the trip unit on this breaker interchangeable?
No, this specific model features a non-interchangeable trip unit. The 225A thermal magnetic assembly is built into the frame and cannot be swapped for a different amperage rating.
Is this circuit breaker HACR rated?
Yes, it is HACR rated. This certification ensures the breaker is safe and approved for use with heating, air conditioning, and refrigeration equipment in commercial and industrial environments.
Has the Siemens JXD6 series been replaced by a newer model?
The JXD6 and Sentron JD frame breakers are considered legacy models by Siemens and are officially being transitioned to the newer 3VA series molded case circuit breakers. However, the JXD63B225 remains widely used for maintaining and expanding existing Sentron installations.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.