Designed for commercial and industrial environments requiring remote shutdown capabilities, this 70-amp QP breaker features a factory-installed 120V shunt trip. It mounts into compatible Siemens load centers and panelboards to provide standard 10kAIC thermal-magnetic protection. The integrated shunt trip mechanism allows facility managers to interface the breaker with emergency stop buttons, fire alarms, or automated control systems.
What does the 00S01 suffix indicate on the Q37000S01 breaker?
The 00S01 suffix designates a factory-installed 120V AC shunt trip. This allows the breaker to be tripped remotely via an external control signal, commonly used for emergency stop circuits or fire alarm interfaces.
What are the wire size and temperature requirements for the Q37000S01 lugs?
The terminals accept 4 AWG to 1/0 AWG copper or 3 AWG to 2/0 AWG aluminum conductors. Because this is a 70A breaker, Siemens requires the use of 75C rated wire.
Which panels accept the Siemens Q37000S01 breaker?
This QP series breaker is designed for plug-in installation in Siemens load centers and panelboards that accept 3-pole, 1-inch per pole branch breakers.
Can the Q37000S01 replace an older ITE breaker with the same catalog number?
Yes. Siemens acquired ITE, and this current production QP breaker is the direct, UL-listed replacement for legacy ITE Q37000S01 models.
Is the Q37000S01 suitable for HVAC applications?
Yes, Siemens QP series breakers are HACR rated, making them compliant for protecting heating, air conditioning, and refrigeration equipment that requires a 70A disconnect.
How much panel space does the Q37000S01 require?
As a 3-pole QP breaker, it requires three standard 1-inch spaces in a compatible load center or panelboard.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.