Designed for comprehensive system protection, the Siemens SHND69120ANGT is a 3-pole, 1200A molded case circuit breaker from the Sentron ND frame family. It mounts into Siemens P5 panelboards, S5 power panels, and Sentron switchboards. Rated at 65 kAIC at 480VAC, this unit-mount breaker is equipped with a microprocessor-based electronic trip unit featuring adjustable Long-Time, Short-Time, Instantaneous, and Ground Fault (LSIG) settings for maximum coordination and safety.

Specifications

Key specifications
Brand Siemens
Part Number SHND69120ANGT
Series SHND6
Amperage 1200A
Poles 3
Mounting Style Unit Mount
Voltage 240VAC, 480VAC, 600VAC
Phase 3
AIC Rating 100kA @ 240VAC, 65kA @ 480VAC, 50kA @ 600VAC
Fit and installation
Frame Type ND
Terminal Type Lugs
For Use With Siemens P5 Panelboards, S5 Power Panels, Sentron Switchboards
Wire Gauge (4) 250-500 kcmil (Al/Cu)
Max Wire 500 kcmil
Min Wire 250 kcmil
Protection and operation
Trip Technology Electronic Trip
Trip Function Code LSIG
Trip Function Long-Time, Short-Time, Instantaneous, Ground Fault
Trip Adjustability Adjustable
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Alarm Switch, Undervoltage Release, Lug Kits
Accessories Lugs Not Included
Standards CSA C22.2 No. 5, IEC 60947-2, UL 489
Approval CSA, IEC, UL
Temp Rating 40C
Construction Features High Interrupting Capacity, HACR Rated, Reverse Feed

Product FAQs

6 answers
What equipment is the Siemens SHND69120ANGT compatible with?

This 1200A ND-frame breaker is designed for use in Siemens P5 panelboards, S5 power panels, and Sentron switchboards.

What wire sizes do the included lugs accept?

The factory lugs on this breaker accept four 250 to 500 kcmil aluminum or copper conductors per phase.

What does the "ANGT" suffix indicate in the SHND69120ANGT catalog number?

The "ANGT" suffix designates an advanced Sensitrip electronic trip unit with LSIG functions, providing adjustable protection for Long-Time, Short-Time, Instantaneous, and Ground Fault conditions.

Does the ground fault function require external components for a 4-wire system?

Yes. While the breaker includes ground fault protection for 3-phase, 3-wire circuits, installing it in a 3-phase, 4-wire system requires a separate neutral current transformer to properly monitor the fourth wire.

What is the difference between the SND6 and SHND6 frame types?

The "H" in the SHND6 prefix designates a high-interrupting rating of 65kAIC at 480V, whereas the standard SND6 frame has a lower interrupting capacity. Both share the same physical dimensions for direct replacement in Sentron gear.

Is the SHND69120ANGT suitable for reverse feed applications?

Yes, Siemens SHND6 solid state circuit breakers are UL Listed for reverse connection applications, allowing them to be back-fed if required by the system design.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.