The Square D BDL36125 is a 3 Pole thermal magnetic molded case circuit breaker with a current rating of 125 Amps and a voltage rating of 600Y/347VAC. It has an interrupting rating of 25kAIC at 2400VAC, 18kAIC at 480VAC. The BDL36125 has a feed-thru connection type and includes long time and instantaneous trip functions.
CSA C22.2 No. 5, EN/IEC 60947-2, NEMA AB 1, UL 489, GB 14048.2, NMX J-266
Approval
CCC, CE, CSA, EAC, IEC, NOM, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Visual Trip Indicator, Reverse Feed
Product FAQs
6 answers
Does the BDL36125 breaker support DIN rail mounting?
Yes, PowerPacT B-Frame unit-mount circuit breakers feature an integrated channel on the back that allows them to snap directly onto a standard 35mm DIN rail. They can also be installed using traditional backpan mounting.
Can I install this unit-mount breaker in a Square D I-Line panelboard?
No. The BDL36125 is designed strictly for backpan or DIN rail installation. For I-Line panelboards, you must use an I-Line specific B-Frame breaker, which will have a catalog number ending in 'A' rather than 'L' (such as BDA36125).
What is the primary advantage of the EverLink lug connections on this breaker?
EverLink lugs feature a patented creep-compensating design with a built-in spring mechanism that maintains continuous tension on the wire conductors. This prevents the connections from loosening over time due to thermal cycling, ensuring a secure and safe electrical connection.
Is the PowerPacT BDL36125 the recommended replacement for legacy F-Frame breakers?
Yes. Schneider Electric introduced the PowerPacT B-Frame series as the direct, modern replacement for older Square D FAL and FHL molded case circuit breakers. It offers improved performance and built-in DIN rail compatibility in a slightly smaller unit-mount footprint.
What is the difference between the BDL36125 and BGL36125 breakers?
The difference is the short-circuit interrupting rating, which is indicated by the second letter in the catalog number. The BDL model features a D-rating (18kA at 480V), while the BGL model has a higher G-rating (35kA at 480V). Both are 125A, 3-pole, unit-mount breakers.
Are the thermal-magnetic trip points on the BDL36125 field adjustable?
No, this breaker utilizes a fixed thermal-magnetic trip unit. Both the long-time (thermal) and instantaneous (magnetic) protection settings are factory calibrated and cannot be adjusted by the user.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 2 reviews.