Square D BGA24040Y2 PowerPacT molded case circuit breaker is rated 40A, 240VAC or 480Y/277VAC, with 2 poles and 1 phase. UL 489 interrupting ratings are 65kA at 208Y/120VAC and 240VAC, 35kA at 480Y/277VAC, and 20kA at 250VDC. It has a thermal magnetic LI trip with fixed thermal and magnetic settings, a B-Frame, I-Line mounting, load side lug terminals and standard protection. The Cu/Al conductor range is 14-2/0 AWG. Dimensions are 5.4 in high, 2.1 in wide and 3.5 in deep. Approvals include CE, UL, EN, IEC, CCC, EAC, CSA, NOM, NEMA, GB and NMX.
CSA C22.2 No. 5, EN/IEC 60947-2, HACR, NEMA AB 1, UL 489
Approval
CCC, CE, CSA, EAC, IEC, NOM, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated
Product FAQs
9 answers
How should I size the Square D BGA24040Y2 for a continuous load?
This breaker has a 40A rated current and an 80% continuous load rating. Select it so the continuous load does not exceed 80% of its rated current, rather than treating 40A as its continuous-load capacity.
What voltage and frequency ratings should I check before selecting this breaker?
The rated voltages are 240VAC and 480Y/277VAC, with a rated frequency of 50/60Hz. Match the circuit voltage and frequency to these ratings; the Y notation indicates a wye system voltage.
What interrupting rating applies at 240VAC?
The UL 489 interrupting rating at 240VAC is 65kA. Compare that rating with the available fault current at the installation point, which must not exceed the breaker's interrupting rating.
Can I adjust the thermal or magnetic trip settings?
Both the thermal and magnetic trip settings are fixed. Thermal-magnetic protection responds to sustained overloads through its thermal element and short circuits through its magnetic element, so selection does not involve field-adjustable trip settings.
What conductor sizes and materials can I terminate at the load lugs?
The load-side lugs accept copper or aluminum conductors from 14 AWG through 2/0 AWG. Use that range to check terminal acceptance, and select conductor size for the circuit's ampacity requirements rather than terminal capacity alone.
What mounting method does this breaker use?
It uses I-Line mounting, with load-side lug connections. Plan the installation around that mounting method and the separate lug terminations for outgoing conductors.
How much physical space should I account for in my layout?
This PowerPacT BG series breaker has a B-Frame and measures 5.4 in high, 2.1 in wide and 3.5 in deep. Use those dimensions for the breaker body when planning the layout, while accounting separately for conductor routing and working access.
What does the HACR marking mean when selecting this breaker?
HACR refers to heating, air conditioning and refrigeration applications. The marking is relevant when equipment instructions call for a HACR circuit breaker; also check the required current, voltage and interrupting ratings.
What operating temperature range should I check for the installation location?
The operating temperature range is -25 to 70 °C. Check the temperature where the breaker will operate, including heat within the enclosure, against that range.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 4.9 out of 5 based on 7 reviews.