Designed to handle demanding electrical loads, the Square D BGA34045Y is a 3-pole, 45A molded case circuit breaker. As part of the PowerPacT B-Frame series, it provides fixed long-time and instantaneous (LI) trip functions for commercial and industrial applications. This breaker installs into Square D I-Line panelboards and switchboards with a factory-configured ABC phase connection. It serves as a substitute for legacy FA34045 units. It offers a 35kAIC interrupt rating at 480Y/277VAC.
CSA C22.2 No. 5, EN/IEC 60947-2, EN/IEC 60947-5-1, GB 14048.2, NEMA AB 1, NMX J-266, UL 489
Approval
CCC, CE, CSA, EAC, IEC, NOM, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Reverse Feed
Product FAQs
6 answers
What panelboards accept the BGA34045Y circuit breaker?
This breaker is designed for use in Square D I-Line panelboards and switchboards. It features an I-Line style plug-in connection that engages directly with the bus stack.
Can the PowerPact BGA34045Y replace older FA frame breakers?
Yes, the PowerPact B-Frame series is the designated replacement for legacy F-Frame breakers. The BGA34045Y can replace older FA34045 I-Line breakers, offering upgraded features while maintaining the same mounting space dimensions for easy retrofitting.
How is the BGA34045Y installed into an I-Line panelboard?
The breaker racks directly onto the I-Line bus stack using its plug-in jaws. Once seated, it is secured in place by tightening the mounting bracket screw to the equipment backpan.
Do the lugs on the BGA34045Y accept both aluminum and copper wire?
Yes, the standard mechanical lugs are rated for both aluminum and copper conductors ranging from 14 AWG to 2/0 AWG. Always use a calibrated torque tool to tighten the wire binding screws to the manufacturer marked specifications to ensure a secure connection.
How does the BGA34045Y protect electrical circuits during a fault?
This breaker utilizes a thermal magnetic trip unit for long-time overload and instantaneous short circuit protection. It also features dual-break rotating contacts that rapidly repel during a fault, significantly reducing let-through currents and enhancing equipment safety.
Can field-installable accessories be added to the BGA34045Y?
Yes, the PowerPact B-Frame platform supports a variety of field-installable accessories. Auxiliary switches, alarm switches, and shunt trips can be installed directly into the designated accessory compartments under the front cover of the breaker.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 4.9 out of 5 based on 7 reviews.