Schneider Electric / Square DBJA260404
Quantity
New
Quantity
Schneider Electric / Square DBJA260404
| Brand | Square D |
|---|---|
| Part Number | BJA260401 |
| Series | BJA |
| Amperage | 40A |
| Poles | 2 |
| Mounting Style | I-Line |
| Voltage | 208Y/120VAC, 240VAC, 480Y/277VAC, 480VAC, 600Y/347VAC, 250VDC |
| Phase | 1 |
| AIC Rating | 100kA @ 208Y/120VAC, 100kA @ 240VAC, 65kA @ 480Y/277VAC, 65kA @ 480VAC, 25kA @ 600Y/347VAC, 50kA @ 250VDC |
| Frame Type | BJA |
|---|---|
| Terminal Type | Lugs |
| For Use With | Square D I-Line Panelboards, Switchboards |
| Wire Gauge | 14-2/0 AWG (Al/Cu) |
| Max Wire | 2/0 AWG |
| Min Wire | 14 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Rotary Handle |
|---|---|
| Accessories | Load Side Lugs Included |
| Standards | CSA C22.2 No 5, EN/IEC 60947-2, GB 14048.2, NEMA AB 1, NMX J-266, UL 489 |
| Approval | CCC, CE, CSA, EAC, IEC, NOM, UL |
| Temp Rating | -25C to 70C |
| Construction Features | HACR Rated, Current Limiting, 80% Rated, Non-Interchangeable Trip, Quick-Make/Quick-Break, Trip-Free Mechanism, Reverse Feed, Phase AB Connection |
This breaker mounts directly into Square D I-Line panelboards and switchboards. It utilizes an I-Line style plug-in connection on the line side and mechanical lugs on the load side.
The factory-installed mechanical lugs accept 14 AWG to 2/0 AWG wire and are rated for both aluminum and copper conductors.
The J-tier interrupting rating provides 65kA at 480VAC and 25kA at 600Y/347VAC.
Yes, this thermal-magnetic breaker is rated for DC systems up to 250VDC, providing an interrupting capacity of 50kA.
"B" designates the PowerPacT B-Frame, "J" indicates the high interrupting rating tier, and "A" specifies the I-Line plug-in mounting style.
The "1" suffix specifies that the breaker comes with factory-installed aluminum mechanical lugs on the off-end (load side), while the line side uses the I-Line plug-in connection.
No, the BJA260401 features a fixed thermal and fixed magnetic trip unit. It provides standard long-time and instantaneous (LI) protection without adjustable dials.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.