Built for demanding environments, the Square D BJA260804 delivers 80 amps of continuous current protection. This 2-pole PowerPacT MCCB utilizes a thermal-magnetic trip unit to safeguard against overloads. Designed for Square D I-Line panelboards, it utilizes a phase BC connection. The breaker is compatible with modern enclosures and seamlessly replaces older FH26080BC models. With a 65 kAIC rating at 480VAC, it ensures reliable fault clearing and features current-limiting technology.
HACR Rated, Current Limiting, Visual Trip Indicator
Product FAQs
8 answers
What panels accept the BJA260804?
This breaker is designed exclusively for use in Square D I-Line panelboards and switchboards. It will not fit in standard load centers or NQ/NF panels.
What phase connection does the BJA260804 use?
The 4 suffix in the catalog number indicates it is configured for a BC phase connection on the I-Line bus. It will draw power specifically from the B and C phases of a 3-phase system.
What older breaker models can the BJA260804 replace?
This PowerPacT B-Frame breaker is a direct replacement for legacy Square D FH26080BC circuit breakers, offering upgraded technology in a compatible form factor.
How does the I-Line mounting system work for this breaker?
The I-Line plug-in design allows the breaker to snap directly onto the panelboard bus stack. This eliminates the need for separate mounting hardware or wire connections to the bus, significantly speeding up installation.
What does the LI trip function indicate on the BJA260804?
The LI designation means the thermal-magnetic trip unit provides Long-Time (overload) and Instantaneous (short-circuit) protection. Both the thermal and magnetic settings are fixed on this model and cannot be adjusted in the field.
Can the BJA260804 be used in DC applications?
Yes, this thermal-magnetic breaker is rated for use in DC systems up to 250VDC, providing a 50kA interrupting capacity for applications like battery backups or industrial DC control panels.
Does this breaker feature current-limiting technology?
Yes, PowerPacT B-Frame breakers like the BJA260804 utilize dual-break rotating contacts. This design reduces peak current and let-through energy during a short-circuit fault, enhancing overall equipment protection.
What frame size is the BJA260804?
It is part of the Square D PowerPacT B-Frame family, which features a compact design with a maximum frame rating of 125 amps.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 4.3 out of 5 based on 3 reviews.