Schneider Electric / Square DBJA261001
Quantity
New
Quantity
Schneider Electric / Square DBJA261001
| Brand | Square D |
|---|---|
| Part Number | BJA261252 |
| Series | BJA |
| Amperage | 125A |
| Poles | 2 |
| Mounting Style | I-Line |
| Voltage | 208Y/120VAC, 240VAC, 480Y/277VAC, 480VAC, 600Y/347VAC, 250VDC |
| Phase | 1 |
| AIC Rating | 100kA @ 208Y/120VAC, 100kA @ 240VAC, 65kA @ 480Y/277VAC, 65kA @ 480VAC, 25kA @ 600Y/347VAC, 50kA @ 250VDC |
| Frame Type | BJA |
|---|---|
| Terminal Type | Lugs |
| For Use With | Square D I-Line Panelboards, Switchboards |
| Wire Gauge | 14-2/0 AWG (Al/Cu) |
| Max Wire | 2/0 AWG |
| Min Wire | 14 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Rotary Handle, Motor Operator |
|---|---|
| Accessories | Phase Connection AC |
| Standards | CSA C22.2 No 5, EN/IEC 60947-2, NEMA AB 1, UL 489 |
| Approval | CCC, CE, CSA, EAC, IEC, NOM, UL |
| Temp Rating | -25C to 70C |
| Construction Features | HACR Rated, Visual Trip Indicator |
Yes, PowerPacT B-frame breakers are designed to replace legacy F-Frame models, including the FA and FH series. They maintain the same mounting space dimensions, allowing for straightforward retrofits in existing Square D I-Line panelboards.
This breaker features a plug-on line side connection that mounts directly to the bus assembly of an I-Line panelboard or switchboard. The load side utilizes mechanical lugs that accommodate 14 to 2/0 AWG aluminum or copper conductors.
In the Square D PowerPacT nomenclature, the J designates the interrupting rating tier. It signifies that the breaker is rated for 65kA at 480VAC and 100kA at 240VAC.
Yes, the BJA261252 is rated for DC applications. It provides an interrupting capacity of 50kA at 250VDC.
This breaker is designed exclusively for use in Square D I-Line panelboards and switchboards. It is not compatible with standard load centers, QO panels, or equipment from other manufacturers.
No, the BJA261252 is equipped with a fixed thermal and fixed magnetic trip unit. The long-time and instantaneous (LI) protection functions are factory calibrated and cannot be modified.
This PowerPacT B-frame breaker features a Visi-Trip indicator, which provides a clear visual cue when the breaker has tripped, allowing for quick identification of circuit issues in the panel.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.