Square D EGB26100 miniature circuit breaker is rated 100A with 2 poles and 600Y/347VAC voltage. It has interrupting ratings of 18kA at 600Y/347VAC, 35kA at 480Y/277VAC and 65kA at 240VAC. This E-Frame breaker features bolt-on mounting, thermal magnetic trip, overcurrent protection, a trip indicator and box lug terminals. Its wire range is 14-2/0 AWG for copper and 12-2/0 AWG for aluminum. It occupies 2 panel spaces, is HACR rated and has cULus approvals.
When should I select the Square D EGB26100 for a circuit?
Select it when the circuit requires 100A overcurrent protection. Coordinate that rating with the calculated load and conductor ampacity.
What does the 600Y/347VAC voltage rating mean for circuit selection?
The 600Y/347VAC rating applies to a grounded-wye AC system. Check both the system voltage and grounding configuration when selecting the breaker.
How do I check the interrupting rating against available fault current?
Use the interrupting rating for the circuit voltage: 18kA at 600Y/347VAC, 35kA at 480Y/277VAC, or 65kA at 240VAC. The available fault current at the installation point must not exceed the applicable rating.
How does the trip mechanism work, and can I adjust it?
The thermal-magnetic mechanism provides long-time protection for sustained overcurrents and instantaneous protection for high-current faults. Both the thermal and magnetic settings are fixed, so selection must account for the load's operating and starting characteristics.
What conductors can I terminate in the box lugs?
The box lugs accept copper conductors from 14-2/0 AWG and aluminum conductors from 12-2/0 AWG. Select conductor size by circuit ampacity requirements as well as the terminal wire range.
What terminal torque should I use?
Apply 34.5 lb-in (3.9 N·m) for 14-10 AWG conductors and 49.6 lb-in (5.6 N·m) for 8-2/0 AWG conductors. Choose the torque by conductor size and use a torque tool to tighten the box-lug connection.
What does HACR rated mean when selecting this breaker?
HACR refers to heating, air-conditioning, and refrigeration applications. This rating supports selection where the equipment calls for a HACR-rated breaker, alongside the required current, voltage, and interrupting ratings.
How does the trip indicator help during troubleshooting?
The trip indicator gives a visual indication that the breaker has tripped. Use it to recognize a protective operation and investigate the cause before resetting.
Why does the 40°C calibration temperature matter?
The thermal trip is calibrated at 40°C, making that temperature the reference for its thermal response. Consider the installation temperature when evaluating overload behavior.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 4.9 out of 5 based on 26 reviews.