Square D FJA34060 Molded Case Circuit Breaker

  • 60A
  • 3 Pole
  • I-Line
Square D FJA34060
Molded Case Circuit Breaker
Brand Square D
SKU FJA34060
Select Item Condition
Earn 465 SuperPoints
  • 60A
  • 3 Pole
  • I-Line

Quantity

Bulk Pricing
Send your parts list for a volume quote.

Square D FJA34060 - 60A 3 Pole Molded Case Circuit Breaker

Re-Certified

$465.00 In Stock

Quantity

Description

Built for overload and short-circuit protection, the Square D FJA34060 molded case circuit breaker is rated 60A, 277/480VAC, with 3 poles and a 65kA interrupting rating at 480VAC. The FJA series breaker has an F frame and I-Line mounting. Fixed thermal magnetic tripping provides long-time and instantaneous protection. Lug terminals support a minimum wire size of 14 AWG. Approvals include CSA, HACR and UL.

Specifications

Key specifications
Brand Square D
Part Number FJA34060
Series FJA
Amperage 60A
Poles 3
Mounting Style I-Line
Voltage 277/480VAC
Phase 3
AIC Rating 65kA @ 480VAC
Fit and installation
Frame Type FJA
Terminal Type Lugs
For Use With Square D I-Line Panelboards and Switchboards
Min Wire 14 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Fixed Magnetic
Standards and features
Available Options Alarm Switch, Auxiliary Switch, Shunt Trip, Undervoltage Release
Standards CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489
Approval CSA, HACR, UL
Temp Rating 40C
Construction Features HACR Rated, High Interrupting Capacity

Product FAQs

9 answers
What current rating should I use when selecting the Square D FJA34060?

This breaker is rated 60A. Select it for a circuit requiring 60A overcurrent protection, with conductor sizing coordinated to the circuit requirements.

How does the voltage rating guide circuit selection?

The breaker is rated 277/480VAC. Match this rating to the circuit voltage when selecting it for an AC application.

How much available fault current can this breaker interrupt at 480VAC?

Its interrupting rating is 65kA at 480VAC. Compare that rating with the available fault current at the installation point to ensure the available fault current does not exceed the breaker's interrupting rating.

How does the trip protection work, and can I adjust it?

Thermal-magnetic protection combines long-time overload protection with instantaneous protection for high fault currents. Both the thermal and magnetic settings are fixed, so select it where preset protection is appropriate rather than field-adjustable trip settings.

What should I consider when selecting conductors for the lug terminals?

The breaker uses lug terminals, with a minimum conductor size of 14 AWG. Choose conductor size for the circuit ampacity rather than treating the terminal minimum as the required circuit wire size.

Why does the 40C temperature rating matter?

The breaker has a 40C temperature rating. Consider installation temperature during selection because its thermal trip element responds to heat when providing overload protection.

What dimensions should I use when planning the installation layout?

The breaker measures 9.75 in high, 3.00 in wide and 5.25 in deep. Use these dimensions to plan the physical space allocated to the breaker.

What does the HACR rating mean for equipment selection?

HACR refers to heating, air-conditioning and refrigeration applications. The HACR rating is relevant when equipment requirements call for a HACR-rated breaker; coordinate the circuit selection with its current, voltage and interrupting ratings.

What does the three-pole construction mean for circuit protection?

The Square D FJA34060 has three poles to interrupt the phase conductors of a three-phase circuit. Plan the phase-conductor terminations across all three poles.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.