Description

Engineered for demanding industrial environments, this 25A TeSys GV3 motor circuit protector offers precise thermal-magnetic tripping. It features an adjustable 17-25A thermal dial alongside fixed magnetic protection. This DIN-rail mounted unit is a direct replacement for the discontinued GV3ME25. It pairs seamlessly with TeSys Deca contactors to form complete motor starters. Equipped with EverLink creep-compensating terminals, it prevents wire loosening over time and resists vibration.

Specifications

Key specifications
Brand Square D
Part Number GV3P25
Series GV3
Amperage 25A
Poles 3
Mounting Style DIN Rail
Voltage 240VAC, 480Y/277VAC, 600Y/347VAC, 208VAC
Phase 3
AIC Rating 100kA @ 240VAC, 50kA @ 480Y/277VAC, 10kA @ 600Y/347VAC
Electrical ratings
Amperage Range 17-25A
Fit and installation
Terminal Type Screw/Clamp Terminal
For Use With TeSys Deca Contactors, TeSys GV3 Accessories
Wire Gauge 14-2 AWG
Max Wire 2 AWG
Min Wire 14 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Adjustable Thermal, Fixed Magnetic
Standards and features
Available Options Auxiliary Switch, Shunt Trip, Undervoltage Release, Busbar System, Padlock Attachment, Mounting Feet
Accessories EverLink Lugs Included
Standards CSA C22.2 No 60947-4-1, EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1
Approval ABS, ATEX, BV, CCC, CSA, DNV-GL, EAC, IEC, LROS, RINA, UKCA, UL
Temp Rating -20C to 60C
Construction Features Phase Loss Protection, Motor Circuit Protector, Trip-Free Mechanism, RoHS Compliant, Mercury Free

Product FAQs

8 answers
Which auxiliary contact blocks are compatible with the GV3P25?

This breaker accepts TeSys GV accessories, including the GVAE11 for front-mounted auxiliary contacts or the GVAN11 for side-mounted signaling.

What are the compatible contactors for building a motor starter with this breaker?

The GV3P25 pairs directly with TeSys Deca contactors, specifically the LC1D25 and LC1D32 models, to build a complete Type 1 or Type 2 motor starter assembly.

What is the magnetic trip current setting?

The fixed instantaneous magnetic trip is factory set at 350 Amps, which is 14 times the maximum rated thermal current, ensuring rapid short-circuit clearance.

What is the maximum 3-phase horsepower rating for this breaker at 480V?

The GV3P25 supports up to 15 HP at 480VAC and up to 20 HP at 600VAC for 3-phase motor applications.

Can this 3-pole breaker be used for single-phase motors?

Yes, it can protect single-phase motors when wired correctly and is rated for up to 1.5 HP at 115VAC and 3 HP at 230VAC.

How do the terminals secure the wiring on this device?

It utilizes EverLink BTR screw clamp terminals, which provide constant tightening pressure to prevent wires from loosening due to thermal cycling or vibration.

How is the breaker secured inside an electrical enclosure?

The compact 55mm wide GV3 frame snaps directly onto a standard 35mm DIN rail for quick panel mounting.

How does the rotary operator indicate a fault?

When a fault occurs, the rotary knob automatically moves to a distinct Trip position. The knob can also be padlocked in the Off position for secure lockout/tagout (LOTO) procedures during maintenance.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.