Square D HDA36100U43X molded case circuit breaker is rated 100A with 3 poles, 600VAC and 250VDC rated voltages, and an 80% continuous load rating. Interrupting ratings are 25kA at 240VAC, 18kA at 480VAC, 14kA at 600VAC and 20kA at 250VDC. This PowerPacT H-Frame breaker features an adjustable electronic LSI trip, a MicroLogic 5.2 A trip unit, I-Line mounting and a load side lug terminal connection. It is HACR Rated, with a rated frequency of 50/60Hz and a conductor range of 14-3/0 AWG (Cu/Al).
CSA C22.2 No. 5, HACR, IEC 60947-2, NEMA AB 1, UL 489
Approval
CE, CSA, IEC, NOM, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated
Product FAQs
8 answers
How should I apply the 100A rating of the Square D HDA36100U43X to continuous loads?
The breaker has a 100A rated current and an 80% continuous load rating. Use the continuous load rating when sizing circuits that carry sustained loads.
What protection does the adjustable electronic LSI trip offer?
The MicroLogic 5.2 A electronic trip unit offers adjustable LSI protection: long-time overload, short-time short-circuit and instantaneous short-circuit protection. These functions let you tailor trip settings to the circuit's protection and coordination requirements.
What conductor materials and sizes can I terminate on the load side?
The load-side lug accepts copper or aluminum conductors from 14 AWG through 3/0 AWG. Choose a conductor within that range that also meets the circuit's ampacity and installation requirements.
How do the three poles and ABC phase connection affect installation?
This is a three-pole breaker for three-phase circuits with an ABC phase connection. Use the ABC connection arrangement to guide phase assignment during installation.
What dimensions should I use when planning the physical layout?
Use a width of 4.09 in, height of 6.4 in and depth of 3.4 in when planning the breaker's physical layout. These dimensions define the breaker body space to account for in the installation design.
What operating temperature range should I consider for the installation?
The operating temperature range is -25 to 70 °C. Choose an installation environment that keeps the breaker within this range during operation.
What does the HACR rating mean when selecting this breaker?
HACR refers to heating, air-conditioning and refrigeration applications. The HACR rating supports selection for those applications, with current, voltage and interrupting ratings chosen to meet the equipment's electrical requirements.
How do I check the frequency rating when selecting this breaker for an AC circuit?
The 50/60Hz rating permits use at either rated AC frequency. Match the system frequency to this rating, and check voltage and interrupting ratings when selecting the breaker.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.