Built for advanced control applications, this 100A, 3-pole PowerPacT HDM breaker integrates seamlessly into Square D switchboards and motor control centers. The unit-mount design includes a factory-installed 120VAC shunt trip, enabling remote disconnection for emergency stops or automated safety systems. Rated for 18kAIC at 480V, it utilizes a Micrologic 3.2 electronic trip unit.
What does the "U31X" suffix indicate on the HDM36100U31XSA?
The U31X suffix designates a Micrologic 3.2 electronic trip unit. This provides standard Long-Time and Instantaneous (LI) protection with adjustable dials for precise system coordination, unlike fixed thermal-magnetic units.
What does the "SA" suffix mean on this Square D circuit breaker?
The SA suffix indicates the breaker is equipped with a factory-installed 120VAC shunt trip accessory. This allows the breaker to be tripped remotely via a control signal for emergency stops or automated safety systems.
Can I install the HDM36100U31XSA in an I-Line panelboard?
No. The "M" in the HDM prefix indicates this is a unit-mount (feed-thru) breaker designed for switchboards, motor control centers, and industrial control panels. It does not have the plug-on jaw connections required for I-Line panelboards.
Does this breaker require a separate control power source for the shunt trip?
Yes, the factory-installed shunt trip (SA suffix) requires a dedicated 120VAC control power source to operate the remote tripping mechanism.
How does the HDM36100U31XSA differ from an HDA-prefix breaker?
The HDM prefix indicates a unit-mount (feed-thru) breaker with lugs on both ends. An HDA prefix indicates an I-Line plug-on breaker designed specifically for Square D I-Line panelboards.
Is the Micrologic 3.2 trip unit interchangeable on the HDM36100U31XSA?
No. Because this specific catalog number lacks a "T" or "R" suffix after the amperage rating, the trip unit is factory-sealed and cannot be field-replaced. If a different trip function is required, the entire breaker must be replaced.
What safety precautions should be taken before wiring the shunt trip on the HDM36100U31XSA?
Ensure all power sources, including the separate 120VAC control power for the shunt trip, are completely de-energized and locked out before making any wiring connections.
Can the HDM36100U31XSA replace older Square D 100A unit-mount breakers?
It can physically replace older 100A unit-mount breakers in compatible Square D switchboards, but because it includes a Micrologic electronic trip unit and a 120VAC shunt trip, you must ensure your control wiring and coordination requirements match these specific features.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.