Part of the PowerPacT H-Frame series, this 60A thermal-magnetic breaker delivers reliable long-time and instantaneous (LI) protection for commercial facilities. The unit features fixed thermal and magnetic trip settings alongside a factory-configured AC phase connection. Designed to install into Square D I-Line panelboards and switchboards, it serves as a robust upgrade for legacy FA26060AC and FH26060AC models. With a 100kA interrupting rating at 240VAC, it ensures superior fault clearing.
Current Limiting, HACR Rated, Visual Trip Indicator, Non-Interchangeable Trip, Reverse Feed, Phase Connection AC
Product FAQs
6 answers
Can the HJA260602 replace older F-frame circuit breakers in an existing panel?
Yes. Square D PowerPacT H-frame I-Line breakers are designed to fit into existing I-Line panelboards and switchboards. They serve as a direct, modernized replacement for legacy FA and FH frame breakers while maintaining the same mounting space requirements.
What does the final digit in the HJA260602 catalog number indicate?
The final digit specifies the factory-configured phase connection for the panelboard bus. For this specific model, the 2 indicates it is configured for an AC phase connection.
Which replacement lug kit is compatible with the load side of this breaker?
The HJA260602 uses the AL150HD mechanical lug kit. These factory-installed lugs accept 14 AWG to 3/0 AWG aluminum or copper conductors and can be replaced in the field if damaged or stripped.
Can this breaker be used in DC control panels or battery systems?
Yes, the HJA260602 is UL listed for direct current applications up to 250VDC, making it suitable for DC control circuits and battery backup systems. It provides a 20kAIC interrupting rating at this voltage.
How is the line side of this breaker connected to the panel?
The HJA260602 features an I-Line style plug-on connection on the line side. The breaker jaws press directly onto the panelboard bus assembly, eliminating the need for line side wiring and speeding up installation.
Can the trip settings on the HJA260602 be adjusted in the field?
No. This breaker is equipped with a traditional thermal magnetic trip unit featuring fixed thermal and fixed magnetic settings. If adjustable trip curves are required, a breaker with a Micrologic electronic trip unit is necessary.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.