Engineered for industrial power distribution, the Square D HJA36100 is a 100A, 3-pole molded case circuit breaker. It belongs to the highly regarded PowerPact H-Frame series, offering dependable thermal-magnetic protection for commercial facilities. Designed with an I-Line plug-on mounting style, this breaker integrates easily into Square D I-Line panelboards. It is an exact substitute for the older FH36100 model. With an interrupting capacity of 65 kAIC at 480VAC, it handles high faults safely.
What enclosures or panels are compatible with the HJA36100?
This circuit breaker is specifically designed for use in Square D I-Line panelboards and switchboards. It uses an I-Line style plug-on connection on the line side and cannot be installed in standard unit-mount enclosures, DIN rails, or NQ/NF series panels.
Does the HJA36100 support field-installable accessories?
Yes, PowerPacT H-frame circuit breakers support a wide range of field-installable accessories. You can install components like shunt trips, undervoltage releases, and auxiliary switches directly under the front accessory cover without removing the breaker from the panel.
Can I adjust the trip settings on this circuit breaker?
No, the HJA36100 features a thermal-magnetic trip unit with fixed long-time and fixed instantaneous (LI) settings. The magnetic hold current is 900A and the trip current is 1700A. If your application requires adjustable trip settings, you will need to select a breaker equipped with a Micrologic electronic trip unit instead.
What types of wire can be used with the load side lugs?
The standard factory-installed mechanical lugs accept both aluminum and copper (Al/Cu) conductors ranging from 14 AWG to 3/0 AWG. Always apply a quality oxide inhibitor when terminating aluminum conductors and tighten them to the torque specifications printed directly on the breaker label.
What does the J in the HJA36100 part number mean?
The J indicates the interrupting capacity tier for this PowerPacT H-frame breaker. A J-tier rating provides 100 kAIC at 240 VAC and 65 kAIC at 480 VAC. If your system requires lower fault protection, you might cross-reference to the G-rated (HGA) or D-rated (HDA) versions.
Does this standard breaker provide ground-fault protection?
Out of the box, this standard thermal-magnetic breaker does not provide equipment ground-fault protection. If ground-fault sensing is required for your installation, you must add a compatible Earth Leakage Module (ELM) or use an advanced breaker with a Micrologic trip unit that includes a G suffix for ground fault.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 4.0 out of 5 based on 1 review.