Square D JGL36250U33X - 250A 3 Pole Molded Case Circuit Breaker

Square D JGL36250U33X - 250A 3 Pole Molded Case Circuit Breaker

New

$3,915.00 In Stock

Quantity

Similar Items

Description

Rated for 35kAIC at 480VAC, this 250A PowerPacT J-Frame breaker offers adjustable LSI trip settings for demanding commercial and industrial environments. It fastens securely into Square D NF panelboards, switchboards, and motor control centers using standard unit-mount hardware. Equipped with true RMS sensing and current-limiting capabilities, the microprocessor-based trip unit allows precise coordination of long-time, short-time, and instantaneous protection parameters.

Specifications

Key specifications
Brand Square D
Part Number JGL36250U33X
Series JGL
Amperage 250A
Poles 3
Mounting Style Unit Mount
Voltage 240VAC, 480VAC, 600VAC
Phase 3
AIC Rating 65kA @ 240VAC, 35kA @ 480VAC, 18kA @ 600VAC
Electrical ratings
Amperage Range 70-250A
Fit and installation
Frame Type JGL
Terminal Type Lugs
For Use With Square D NF Panelboards, Switchboards, Motor Control Centers, Industrial Enclosures
Wire Gauge 3/0 AWG - 350 kcmil (Al/Cu)
Max Wire 350 kcmil
Min Wire 3/0 AWG
Protection and operation
Trip Technology Electronic Trip
Trip Function Code LSI
Trip Function Long-Time, Short-Time, Instantaneous
Trip Adjustability Adjustable
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Motor Operator, Rotary Handle
Accessories Lugs (AL250JD)
Standards CSA C22.2 No 5, HACR, IEC 60947-2, NEMA AB1, NOM-003-SCFI-2000, UL 489
Approval CCC, CE, CSA, IEC, NOM, UL
Temp Rating -25C to 70C
Construction Features HACR Rated, Current Limiting, Visual Trip Indicator, 80% Rated

Product FAQs

10 answers
Is the Square D JGL36250U33X rated for 80% or 100% continuous current?

This breaker is standard 80% rated. For a 100% continuous current rating in the same frame and trip unit, you would need the JGL36250CU33X.

What is the recommended tightening torque for the lugs on the JGL36250U33X?

The standard AL250JD line and load lugs for 3/0 AWG to 350 kcmil aluminum or copper wire should be torqued to 225 lb-in (25 N.m) using a 5/16 inch hex bit.

Can I install the JGL36250U33X in a Square D I-Line panelboard?

No, the JGL36250U33X is a unit mount (feed-thru) circuit breaker designed for individual mounting or use in NF panelboards, switchboards, and enclosures. For an I-Line panelboard, you will need the I-Line version, part number JGA36250U33X.

What is the difference between the JGL36250U31X and the JGL36250U33X?

The JGL36250U31X features a Micrologic 3.2 trip unit with standard LI (Long-time, Instantaneous) protection. The JGL36250U33X features the Micrologic 3.2 S trip unit, which adds Short-time protection (LSI: Long-time, Short-time, Instantaneous) for better system coordination.

Is the Micrologic trip unit on the JGL36250U33X field replaceable?

No. PowerPacT J-Frame breakers require a T or R suffix in the catalog number (e.g., JGL36250TU33X) to indicate a field interchangeable trip unit. The standard JGL36250U33X comes with a factory sealed trip unit that cannot be swapped in the field.

Can the JGL36250U33X be reverse fed?

Yes, the JGL36250U33X is suitable for reverse feeding. However, always verify that your specific application and local electrical codes permit reverse fed installations.

Does the JGL36250U33X include a push-to-trip button for testing?

Yes, like all PowerPacT J-Frame circuit breakers, it features an integral push-to-trip button on the cover. This allows you to manually trip the breaker to verify the mechanical operation of the tripping mechanism.

Are auxiliary switches or shunt trips field installable on the JGL36250U33X?

Yes, PowerPacT J-Frame breakers support a wide range of field installable internal accessories, including auxiliary switches, alarm switches, shunt trips, and undervoltage releases. These install behind the front cover of the breaker.

What does the LSI designation mean on the Micrologic 3.2 S trip unit?

LSI stands for Long-time, Short-time, and Instantaneous protection. Long-time protects against sustained overloads, Short-time provides a delayed trip for short circuits to allow downstream breakers to clear the fault first, and Instantaneous trips immediately under severe short circuit conditions.

Is the JGL36250U33X rated for use in DC applications?

No. While some thermal magnetic J-Frame breakers have DC ratings, breakers equipped with electronic Micrologic trip units, like the JGL36250U33X, are rated for AC voltage only.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.