Designed for heavy-duty commercial applications, the Square D KH36175 is a 175-amp, 3-pole molded case circuit breaker. It features fixed thermal and adjustable magnetic trip functions (LI) to handle demanding electrical loads. As a K-Frame device, it plugs securely into standard Square D I-Line panelboards and switchboards. Facilities looking to modernize can cross-reference this legacy unit to the newer PowerPact JJA36175.
Is the Square D KH36175 still actively manufactured?
No, the KH36175 is a legacy K-frame molded case circuit breaker that is no longer in active production. However, it remains a common component for servicing older electrical distribution systems without requiring a complete panel retrofit.
What is the modern replacement for the KH36175?
Facilities looking to upgrade to current technology can cross-reference this breaker to the Square D PowerPact JJA36175. This is a modern 175A I-Line breaker that fits the same panels while offering updated internal mechanisms and higher interrupting ratings.
How is the KH36175 breaker installed?
This breaker utilizes Square D's I-Line plug-in mounting system. The line side features spring-loaded jaws that push directly onto the panelboard bus stack, while the load side relies on standard mechanical lugs for wire termination.
What type of panels accept the KH36175?
The KH36175 is strictly compatible with Square D I-Line panelboards and switchboards. It will not fit in standard load centers or bolt-on distribution panels due to its specialized plug-on phase connections.
How does the adjustable trip unit on the KH36175 function?
The breaker features a thermal-magnetic trip unit. The thermal element provides fixed long-time protection against overloads, while the magnetic element features an adjustable dial to dial in precise instantaneous short-circuit protection.
Can the KH36175 be used in DC electrical applications?
Yes, in addition to standard AC systems, the KH36175 is rated for direct current applications up to 250VDC. In a DC system, it provides a maximum short-circuit interrupting capacity of 10kAIC.
What wire sizes are supported by the lugs on the KH36175?
The factory load side mechanical lugs are designed to accept copper or aluminum (Al/Cu) conductors ranging from 4 AWG up to 350 kcmil.
What ambient temperature is this breaker calibrated for?
The KH36175 is factory calibrated for a standard ambient operating temperature of 40 degrees Celsius (104 degrees Fahrenheit). Environments consistently exceeding this threshold may require load derating to prevent nuisance tripping.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 1 review.