Providing advanced control, the LC36450-1021 is a 3-pole, 450A MCCB. It features a factory-installed 120-240VAC shunt trip for remote disconnection. This L-Frame breaker mounts into Square D I-Line panelboards. It is replaced by the LJA36600U31X, which requires a separate shunt trip accessory and trip adjustment to 450A. Delivering 65 kAIC at 480VAC, it utilizes thermal-magnetic technology with LI protection. Load-side lugs are included for 4/0 AWG to 500 kcmil wiring.
Shunt Trip (Factory Installed), Load Side Lugs Included
Standards
CSA C22.2 No. 5, HACR, IEC 60947-2, NEMA AB 1, UL 489
Approval
CSA, IEC, UL
Temp Rating
40C
Construction Features
HACR Rated, Extra High Interrupting Capacity
Product FAQs
7 answers
What does the -1021 suffix indicate on the LC36450-1021 catalog number?
The -1021 suffix designates a factory-installed 120/240VAC shunt trip, allowing the breaker to be tripped remotely for emergency stops or control system integration.
Can I install the LC36450-1021 in a standard Square D QO or Homeline load center?
No, this breaker features an I-Line plug-in connection and is strictly compatible with Square D I-Line panelboards and switchboards.
What are the conductor requirements for the LC36450-1021 lugs?
The breaker is equipped with lugs that accept two 4/0 AWG to 500 kcmil conductors per phase. Both aluminum and copper wires are supported.
Are the thermal and magnetic trip settings adjustable on the LC36450-1021?
The thermal protection for overload conditions is fixed, while the magnetic protection for short circuits is adjustable to coordinate with downstream devices.
What does the LI trip function code mean on this breaker?
The LI designation indicates that the thermal-magnetic trip unit provides Long-Time (L) protection for overloads and Instantaneous (I) protection for short circuits.
Is the LC36450-1021 rated for direct current (DC) systems?
Yes, in addition to its AC ratings, this breaker is rated for 250VDC applications with a 10kA interrupting capacity.
Is the LC36450-1021 a modern PowerPact breaker?
No, it is a legacy Square D L-Frame molded case circuit breaker. It serves as a direct replacement for existing legacy LC frame installations.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 1 review.