Built for circuit protection, Square D LLA36400U53X is a 400A, 3-pole molded case circuit breaker. The 3-phase PowerPacT L breaker uses an L frame and I-Line mounting. Its electronic trip provides long-time, short-time and instantaneous functions with adjustable thermal and magnetic settings. Interrupting ratings are 125kA at 240VAC, 100kA at 480VAC and 50kA at 600VAC. Approvals include CSA, IEC, NOM and UL.
Can I adjust the current setting on the Square D LLA36400U53X below 400A?
This 400A breaker has an adjustable trip range of 160-400A. Select the setting to coordinate overload protection with the circuit conductors and load requirements.
How do I select this breaker for the available fault current?
The interrupting ratings are 125kA at 240VAC, 100kA at 480VAC and 50kA at 600VAC. Use the rating at your circuit voltage and ensure it is at least equal to the available fault current at the installation point.
What does the LSI electronic trip do?
LSI means long-time, short-time and instantaneous protection. Long-time protection addresses sustained overloads, short-time protection allows a controlled delay for coordination, and instantaneous protection acts without intentional delay on high fault currents.
What does current limiting mean when selecting this breaker?
Current limiting reduces the peak current and energy let through during faults within the breaker's current-limiting operating region. This feature helps reduce fault stress on downstream conductors and equipment.
Can I use this breaker where equipment calls for HACR-rated protection?
This breaker is HACR rated for heating, air-conditioning and refrigeration applications. Use that rating as a selection criterion when the equipment requires HACR-rated circuit protection.
How does the three-pole construction apply to a three-phase circuit?
The breaker has three poles for a three-phase circuit. A three-pole breaker interrupts the three phase conductors together, allowing the circuit to be disconnected as a unit.
What temperature range should I consider when selecting this breaker?
The temperature rating is -25C to 70C. Compare that range with the temperatures expected where the breaker will be installed.
What dimensions should I use for installation layout planning?
The breaker measures 13.40 in high, 5.50 in wide and 4.30 in deep. Use these dimensions for layout planning, with additional space allocated for wiring and operation.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.