Delivering advanced protection for industrial power systems, the ME36600LS provides 600A of 3-pole capacity. It utilizes a Micrologic trip unit with adjustable long-time and short-time (LS) functions, allowing for precise system coordination and true RMS sensing. Rated at 65kAIC at 480VAC, it easily mounts into Square D I-Line switchboards and panelboards. For modern upgrades, this legacy M-Frame breaker crosses over to the PowerPact LJA36600U33X or PJA36060U33A.
What type of enclosures accept the ME36600LS circuit breaker?
It is specifically designed to mount in Square D I-Line panelboards and switchboards. The plug-in jaw design is not compatible with NQ, NF, or standard QO load centers.
What do the "LS" trip functions mean on this breaker?
The LS indicates that the built-in electronic trip unit has adjustable Long-Time and Short-Time protection parameters. This allows panel builders to fine-tune the overload and short-circuit response curves for better coordination with downstream devices compared to standard thermal-magnetic breakers.
Does the ME36600LS require a separate mounting base?
No separate base is needed for the line connection. The I-Line construction includes integral plug-in jaws that attach directly to the panel bus bar, meaning you only need to wire the load side lugs.
What is the modern replacement for the legacy ME36600LS?
The legacy ME series was superseded by the Square D PowerPact family. Upgrading to a modern equivalent typically involves selecting a PowerPact L-frame or P-frame breaker with an I-Line connection, matching your specific 600-amp load and interrupting rating requirements.
Is this electronic trip breaker suitable for reverse feeding?
Molded case circuit breakers with electronic trip units are generally not rated for reverse feeding unless explicitly labeled. The line and load connections must be wired exactly as marked on the breaker face to ensure the solid-state circuitry functions correctly.
How many cables can the load side lugs accept?
The standard load lugs on this 600-amp breaker accept up to three conductors per phase. The lugs are dual-rated for aluminum or copper wire ranging from 3/0 AWG to 500 kcmil.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 1 review.