Engineered for commercial and industrial applications, the Square D QDA221252 is a 2-pole, 125A molded case circuit breaker from the PowerPacT Q-Frame family. It provides robust overcurrent protection with fixed thermal and magnetic trip units. This unit mounts into Square D I-Line panelboards and serves as an exact replacement for the legacy Q221252 breaker. Rated for 25kAIC at 240VAC, it features an AC phase connection and includes load-side lugs accommodating 4 AWG to 300 kcmil wire.
What type of panelboard is required for the QDA221252 circuit breaker?
This breaker features an I-Line style plug-in connection and is designed exclusively for use in Square D I-Line panelboards and switchboards. It is not compatible with NQ or NF series panels.
What is the recommended tightening torque for the load lugs on this breaker?
The load lugs on the QDA221252 require a tightening torque of 248 lb-in (28 N.m) for 4 AWG to 300 kcmil aluminum or copper wire.
Can the QDA221252 be used to replace an older Q2 series breaker?
Yes, PowerPacT Q-frame circuit breakers are direct replacements for legacy Square D Q2 series devices of the same pole and amperage configuration.
Is the QDA221252 rated for use in DC voltage systems?
No, PowerPacT Q-frame circuit breakers are designed and rated strictly for AC systems up to 240VAC. They do not carry a DC voltage rating.
Can this I-Line circuit breaker be reverse fed?
Yes, Square D PowerPacT Q-frame I-Line breakers can be reverse fed for supply side applications, provided they are properly marked as a main breaker in accordance with panelboard requirements.
What is the difference between the QDA221252 and the QGA221252?
The difference is the interrupting rating. The QDA221252 has a 25kAIC rating at 240VAC, while the QGA221252 has a higher 65kAIC rating at 240VAC. Both share the same physical footprint and I-Line mounting.
Does this breaker require a separate mounting bracket for installation in an I-Line panel?
No, the QDA221252 features an integral I-Line plug-on bracket on the line side that mounts directly to the panelboard bus stack. No additional mounting hardware is required.
Are the trip settings on the QDA221252 adjustable?
No, this breaker uses a thermal magnetic trip unit with fixed Long-Time and Instantaneous protection. The thermal and magnetic trip points are factory set and non-adjustable.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 6 reviews.