Skip to main content
Expedited shipping available at checkout

Eaton / Westinghouse JK3150 Molded Case Circuit Breaker

  • 150A
  • 3 Pole
  • Unit Mount
Eaton / Westinghouse JK3150
Molded Case Circuit Breaker
Brand Eaton / Westinghouse
SKU JK3150
Select Item Condition
Earn 458 SuperPoints
  • 150A
  • 3 Pole
  • Unit Mount

Quantity

Bulk Pricing
Send your parts list for a volume quote.
Westinghouse JK3150 3 Pole Circuit Breaker

Eaton / Westinghouse JK3150 - 150A 3 Pole Molded Case Circuit Breaker

Re-Certified

$458.38 In Stock

Quantity

Similar Items

Description

The Eaton JK3150 is a 3-pole, 150A molded case circuit breaker designed for commercial and industrial power distribution. Built with a rugged Series C J-Frame architecture, it provides dependable overcurrent protection. This unit mount breaker installs into legacy Westinghouse panelboards, switchboards, and motor control centers. It serves as an exact drop-in replacement for discontinued JDB3150 and HJD3150 breakers. It features a 65kAIC rating at 240V and fixed thermal-magnetic trip functions.

Specifications

Key specifications
Brand Eaton / Westinghouse
Part Number JK3150-R
Series JK
Amperage 150A
Poles 3
Mounting Style Unit Mount
Voltage 240VAC, 480VAC, 600VAC, 250VDC
Phase 3
AIC Rating 65kA @ 240VAC, 30kA @ 480VAC, 18kA @ 600VAC, 10kA @ 250VDC
Fit and installation
Terminal Type Lugs
For Use With Westinghouse Panelboards, Switchboards, Motor Control Centers, Eaton Series C Panelboards
Wire Gauge 4 AWG - 350 kcmil (Al/Cu)
Max Wire 350 kcmil
Min Wire 4 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Adjustable Magnetic
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch
Accessories Load Side Lugs
Standards CSA C22.2 No. 5, NEMA AB-1, UL 489
Approval CSA, UL
Temp Rating 40C
Construction Features HACR Rated, High Interrupting Capacity

Product FAQs

8 answers
What panelboards are compatible with the JK3150 circuit breaker?

The JK3150 is designed for use in legacy Westinghouse panelboards, switchboards, and motor control centers, as well as Eaton Series C panelboards.

Can the JK3150 replace older discontinued breakers?

Yes, the JK3150 serves as an exact drop-in replacement for discontinued JDB3150 and HJD3150 circuit breakers.

What wire sizes are accepted by the lugs on the JK3150?

The load side lugs accept 4 AWG to 350 kcmil aluminum or copper wire.

How does the trip unit on the JK3150 operate?

It features a thermal-magnetic trip unit with a fixed thermal element for overload protection and an adjustable magnetic element, allowing you to set the instantaneous short-circuit trip threshold.

Does the JK3150 breaker include lugs?

Yes, this unit mount breaker comes complete with load side lug terminals for wire connections.

Is the JK3150 rated for DC applications?

Yes, in addition to its AC ratings, this breaker is rated for up to 250VDC with a 10kA interrupting capacity.

Is the JK3150 suitable for HVAC applications?

Yes, this breaker is HACR rated, making it suitable for use with heating, air conditioning, and refrigeration equipment.

What does the LI trip function code indicate on the JK3150?

The LI designation means the breaker provides Long-Time (L) overload protection and Instantaneous (I) short-circuit protection.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.