Built for precise 3-phase protection, the Siemens 3VA5195-4EC31-0AA0 15A molded case circuit breaker utilizes the compact 125A 3VA5 frame. It stands out with its TM230 trip unit, which combines fixed thermal overload defense with an adjustable magnetic short-circuit response. Rated for Class S breaking capacity (25kAIC at 480V), it mounts into Siemens 3VA panelboards and switchboards. When paired with a retrofit kit, it serves as an upgrade for discontinued ED63B015 breakers.
Auxiliary Switch, Alarm Switch, Shunt Trip, Undervoltage Release, Motor Operator
Accessories
None (Without Connection)
Standards
IEC 60947-2, UL 489, CSA C22.2 No. 5
Approval
ABS, CE, CSA, EAC, UL, VDE
Temp Rating
-25C to 70C
Construction Features
HACR Rated
Product FAQs
7 answers
Are lugs included with the 3VA5195-4EC31-0AA0 circuit breaker?
No, the 0AA0 suffix indicates this breaker is shipped without lugs. Lugs or nut keepers must be ordered separately for field installation in panelboards or switchboards.
Which legacy Siemens breakers does the 3VA5195-4EC31-0AA0 replace?
This breaker is the modern 3VA series equivalent for legacy 15A, 3-pole ED4, ED6, and NGG frame breakers, including catalog numbers ED43B015, ED63B015, and NGG3B015.
What is the frame size of the 3VA5195-4EC31-0AA0?
This breaker belongs to the 3VA51 frame class, which has a maximum continuous current rating of 125A.
What type of trip unit is installed in the 3VA5195-4EC31-0AA0?
It features a TM230 thermal-magnetic trip unit. This provides fixed thermal overload protection and adjustable magnetic short-circuit protection.
What is the magnetic trip adjustment range for this 15A breaker?
The TM230 trip unit on this 15A model has an adjustable magnetic short-circuit protection range of 150A to 300A.
Is the 3VA5195-4EC31-0AA0 suitable for reverse feed applications?
Yes, all Siemens 3VA5 thermal-magnetic circuit breakers are UL listed for reverse feed applications.
Can the 3VA5195-4EC31-0AA0 be used in direct current (DC) systems?
Yes, this breaker is rated for DC applications up to 500VDC. When applying thermal-magnetic MCCBs in DC systems, poles are typically wired in series depending on the system voltage. Consult Siemens documentation for specific DC wiring configurations.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 4.8 out of 5 based on 8 reviews.