Delivering 30 amps of reliable overcurrent defense, the Siemens NGG2B030L serves heavy-duty industrial environments. This 2-pole unit-mount MCCB operates on systems up to 480VAC and 600Y/347VAC. It integrates seamlessly into Siemens enclosures, switchboards, and DIN rail setups. Facilities upgrading older infrastructure can replace this unit with the newer 3VA5130-4ED21-0AA0. With a 65kAIC rating at 240V, it comes equipped with TC1Q1 lugs accepting 14-6 AWG copper wiring.
Siemens Enclosures, Control Panels, Switchboards, DIN Rail
Wire Gauge
14-6 AWG (Cu), 12-6 AWG (Al)
Max Wire
6 AWG
Min Wire
14 AWG (Cu), 12 AWG (Al)
Protection and operation
Trip Technology
Thermal Magnetic
Trip Function Code
LI
Trip Function
Long-Time, Instantaneous
Trip Adjustability
Fixed Thermal, Fixed Magnetic
Standards and features
Available Options
Shunt Trip, Auxiliary Switch, Alarm Switch
Accessories
Line and Load Lugs Included (TC1Q1)
Standards
CSA C22.2 No. 5, IEC 60947-2, UL 489
Approval
CE, CSA, HACR, HID, NOM, UL
Temp Rating
40C
Product FAQs
7 answers
What wire sizes are compatible with the NGG2B030L lugs?
The factory lugs accept 14 to 6 AWG copper wire or 12 to 6 AWG aluminum wire.
How is the NGG2B030L installed in a panel?
This is a unit mount, feed-thru breaker. It is designed to be bolted directly to the chassis or mounted on a DIN rail within compatible Siemens enclosures, control panels, or switchboards.
Is the NGG2B030L suitable for direct current (DC) systems?
Yes, this breaker is rated for DC applications, providing up to 14kA interrupting capacity at 125 or 250VDC.
Can the trip settings be adjusted in the field?
No, the thermal and magnetic trip elements on this GG frame breaker are fixed and cannot be adjusted.
What type of protection does the LI trip unit provide?
The LI designation means it includes Long-Time protection for standard overloads and Instantaneous protection for short circuits.
What frame family does the NGG2B030L belong to?
It is part of the Siemens SENTRON series and utilizes the GG frame, which falls under the broader GB/GG frame group.
Does this breaker plug onto a standard panelboard bus?
No, as a unit mount breaker with feed-thru connections, it does not plug onto a busbar. It requires appropriate hardware for surface mounting or DIN rail installation.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.