ABB / General ElectricSKHA36AT0800
Quantity
New
Quantity
ABB / General ElectricSKHA36AT0800
ABB / General ElectricSKLC3608L4XX
ABB / General ElectricSKLL3608L4XX
ABB / General ElectricSKLA36AT0800
| Brand | ABB / General Electric |
|---|---|
| Series | SKHH |
| Amperage | 800A |
| Poles | 3 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480VAC, 600VAC |
| Phase | 3 |
| AIC Rating | 65kA @ 240VAC, 50kA @ 480VAC, 25kA @ 600VAC |
| Amperage Range | 400-800A |
|---|
| Frame Type | SKHH |
|---|---|
| Terminal Type | Lugs |
| For Use With | Spectra Series Panelboards, Spectra Series Switchboards |
| Trip Technology | Electronic Trip |
|---|---|
| Trip Function Code | LSI |
| Trip Function | Long-Time, Short-Time, Instantaneous |
| Trip Adjustability | Adjustable |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Bell Alarm, Lug Kits, Communication Module, Padlock Attachment |
|---|---|
| Accessories | MicroEntelliGuard Trip Unit (LSI) |
| Standards | CSA C22.2 No. 5, IEC 60947-2, UL 489 |
| Approval | CE, CSA, UL |
| Temp Rating | -20C to 55C |
| Construction Features | 100% Rated, HACR Rated, Reverse Feed, True RMS Sensing, Interchangeable Trip Unit, Trip-Free Mechanism |
This SK frame breaker is designed for installation in GE Spectra Series panelboards and Spectra Series switchboards.
Yes, GE Spectra RMS SK frame breakers utilize interchangeable rating plugs to set the continuous current limit. A compatible rating plug, such as the SRPK800B800, must be installed in the electronic trip unit for the breaker to operate properly.
The SKHH3608L3XX features a bolt-on mounting configuration and comes equipped with standard lugs for wire terminations. Verify specific wire range and torque requirements based on the installed lug kit before wiring.
Originally developed by General Electric as part of the Spectra RMS line, this breaker is now manufactured by ABB following their acquisition of GE Industrial Solutions. Both ABB and GE branded versions share the exact same physical frame and performance specifications.
Yes. The second H in the SKHH catalog prefix indicates that this is a 100 percent continuously rated circuit breaker, meaning it can safely carry its full 800-amp load continuously when installed in an appropriately sized and ventilated enclosure.
The LSI designation indicates that the solid state electronic trip unit features adjustable Long-Time, Short-Time, and Instantaneous protection settings. This allows for highly precise overcurrent and short-circuit coordination within complex electrical distribution systems.
No, the SKHH3608L3XX features an LSI trip unit consisting of Long-Time, Short-Time, and Instantaneous protection. If your system requires equipment ground fault protection, a breaker with an LSIG trip function is required.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.