Delivering reliable thermal-magnetic (LI) protection, the HKD3400X15 is a 400A, three-pole MCCB from Eaton. It is built to handle the rigorous demands of commercial power systems. This K-frame model installs into Series C panelboards and switchboards. The "X15" suffix denotes a factory configuration that includes load-side lugs (3TA401K), streamlining installation. Capable of interrupting 65 kAIC at 480VAC, it provides exceptional fault-clearing performance and features reverse feed capability.
HACR Rated, High Interrupting Capacity, Reverse Feed, Interchangeable Trip Unit
Product FAQs
6 answers
What does the X15 suffix indicate on the HKD3400X15?
The X15 suffix indicates a factory configuration designed for panelboard installation. It includes standard mechanical lugs on the load side, while the line side is left without lugs for direct connection to the busbar.
What wire sizes are accepted by the load lugs on this breaker?
The load-side lugs accept either one 2/0 AWG to 500 kcmil conductor or two 2/0 AWG to 250 kcmil conductors per phase. They are rated for use with both copper and aluminum wiring.
Can the HKD3400X15 replace a standard KD3400 breaker?
Yes, the HKD is the high-interrupting version of the standard KD frame. Both are Series C K-frame breakers with identical physical dimensions, making the HKD3400X15 a direct drop-in replacement that provides a higher short-circuit rating.
Is the trip unit on the HKD3400X15 fully adjustable?
The thermal element for long-time protection is fixed at 400 amps, but the magnetic instantaneous trip is adjustable. This allows electricians to fine-tune the short-circuit response to coordinate with downstream devices and prevent nuisance tripping from motor inrush currents.
Which enclosures and panelboards are compatible with this breaker?
The HKD3400X15 is designed for use in Eaton and Cutler-Hammer Series C panelboards, switchboards, and motor control centers that are configured to accept K-frame circuit breakers.
Does this breaker include ground fault protection?
No, the HKD3400X15 features an LI (Long-Time, Instantaneous) trip unit, which does not include ground fault protection. If ground fault monitoring is required, a breaker with an LSG or LSIG trip unit must be used.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 4 reviews.