Eaton / Cutler-HammerCRD316T36W
Quantity
New
Quantity
Eaton / Cutler-HammerCRD316T36W
Eaton / Cutler-HammerRD320T32W
| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | CRD320T33W |
| Series | CRD |
| Amperage | 2000A |
| Poles | 3 |
| Mounting Style | Unit Mount |
| Voltage | 240VAC, 480VAC, 600VAC |
| Phase | 3 |
| AIC Rating | 125kA @ 240VAC, 65kA @ 480VAC, 50kA @ 600VAC |
| Amperage Range | 1000-2000A |
|---|
| Frame Type | CRD |
|---|---|
| Terminal Type | Lugs |
| For Use With | Eaton Series C Panelboards, Switchboards, Motor Control Centers |
| Trip Technology | Electronic Trip |
|---|---|
| Trip Function Code | LS |
| Trip Function | Long-Time, Short-Time |
| Trip Adjustability | Adjustable |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Motor Operator |
|---|---|
| Accessories | Digitrip 310 Trip Unit |
| Standards | CSA C22.2 No. 5, UL 489 |
| Approval | CSA, UL |
| Temp Rating | 40C |
| Construction Features | 100% Rated, HACR Rated, Reverse Feed, True RMS Sensing |
The T33W designates an electronic Digitrip 310 trip unit equipped with LS (Long-Time and Short-Time) protection functions. This allows for adjustable overload and short-circuit coordination.
No, this breaker is supplied without terminals. For a 2000A application, you will typically need a multi-barrel lug kit such as the Eaton TA2000RD, which accommodates up to six #2 AWG to 600 kcmil conductors per phase.
This Series C R-frame breaker is designed for bolt-on unit mount installation in Eaton and Cutler-Hammer switchboards, motor control centers, and panelboards.
Yes, Eaton Series C R-frame breakers are backward compatible and can directly replace legacy Cutler-Hammer and Westinghouse R-frame breakers with matching specifications.
The LS functions allow you to adjust the continuous current setting (Long-Time pickup and delay) for overload protection, as well as the Short-Time pickup and delay for selective coordination.
Yes, the C prefix in the CRD frame designation indicates that this breaker is 100% rated. This means it can carry its full 2000A continuous current rating when installed in an appropriately sized and ventilated enclosure.
No, the LS designation indicates this trip unit provides Long-Time and Short-Time protection only. It lacks an Instantaneous (I) function, making it suitable for specific coordination schemes where a downstream breaker is intended to clear instantaneous faults.
Always ensure the breaker is de-energized or appropriate arc flash PPE is worn before accessing the trip unit panel. Adjustments should only be made by a qualified electrician following a properly engineered coordination study to prevent nuisance tripping or equipment damage.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.