| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | EGC3070FFG |
| Series | EGC |
| Amperage | 70A |
| Poles | 3 |
| Mounting Style | Unit Mount |
| Voltage | 240VAC, 480VAC, 600Y/347VAC, 125/250VDC |
| Phase | 3 |
| AIC Rating | 200kA @ 240VAC, 100kA @ 480VAC, 35kA @ 600Y/347VAC, 42kA @ 125/250VDC |
| Frame Type | EGC |
|---|---|
| Terminal Type | Lugs |
| For Use With | Eaton Series G Panelboards, Pow-R-Line Panelboards, Switchboards, Motor Control Centers |
| Wire Gauge | 14-1/0 AWG (Al/Cu) |
| Max Wire | 1/0 AWG |
| Min Wire | 14 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Motor Operator, Rotary Handle, Handle Lock |
|---|---|
| Accessories | Line and Load Terminals (3TA125EF), Mounting Hardware |
| Standards | CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489 |
| Approval | CE, CSA, IEC, KEMA, UL |
| Temp Rating | -20C to 70C |
| Construction Features | Current Limiting, High Interrupting Capacity, Reverse Feed, HACR Rated |
This EG-frame breaker is engineered for installation in Eaton Series G and Pow-R-Line panelboards, as well as compatible switchboards and motor control centers.
The factory-installed line and load terminals are rated for both aluminum and copper (Al/Cu) conductors, accepting wire gauges from 14 AWG up to 1/0 AWG.
In Eaton's Series G catalog numbering, "FFG" specifies that the breaker is equipped with a fixed thermal and fixed magnetic trip unit, and that it comes standard with line and load lug terminals.
The "EGC" designation indicates that the breaker belongs to the EG-frame family and features a specific interrupting capacity tier, rated for up to 100 kAIC at 480V.
No, this breaker is built with a non-interchangeable trip unit featuring fixed long-time and fixed instantaneous (LI) protection functions, meaning the trip curve cannot be field-adjusted.
Yes, in addition to its AC ratings, this thermal-magnetic breaker is rated for use in DC circuits up to 125/250VDC with an interrupting capacity of 42 kAIC.
No, this is specifically an EG-frame breaker. While it is part of the broader Series G family, it has a unique physical footprint (5.5 inches high by 3 inches wide) and cannot be swapped into spaces designed for JG, LG, or NG frames.
The maximum interrupting capacity is 200 kAIC when used on a 240VAC system. The rating scales down at higher voltages, providing 100 kAIC at 480VAC and 35 kAIC at 600/347VAC.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.